User manual

page 37
Cyclon Series User Manual – Operation
1.3 Stopping
1. To stop the compressor press
STOP
(B3).
This initiates a controlled shut down
sequence. The compressor will unload, the
drive motor will stop and the Start indicator
(L8) will flash slowly for the blowdown period.
See para 2.3 ‘Program mode settings’.
2. The compressor motor cannot be re-started
during the blowdown sequence. If
START
(B2) is pressed the start indicator will flash
quickly and the compressor will enter the
Standby mode and start automatically when
the blowdown time expires.
CAUTION: The compressor should not be stopped
during a start sequence.
1.4 Emergency Stop
1. When
EMERGENCY STOP
is pressed, the
compressor will stop immediately and the unit
will blow down.
2. Indicators L1 to L8 will flash to show
EMERGENCY STOP
has been pressed.
3. If the
EMERGENCY STOP
button is reset
and
RESET
(B6) pressed during the
blowdown time, the Start indicator will slow
flash for the remainder of the normal
blowdown time.
CAUTION: The Emergency Stop button should be
used only in a genuine emergency and must not
be used as the normal method of stopping the
compressor.
1.5 Oil Temperature and Hours Run Display
1. When the compressor is in normal running
mode indicator L1 will be lit and the display
will show the delivery pressure in Bar.
2. To interrogate the oil temperature, total hours
run or hours run onload, press
VIEW
(B1).
3. Each time
VIEW
is pressed the next indicator
in the sequence L1 to L4 will light and the
display will show the corresponding value.
Indicator Display
L1 Delivery Pressure in Bar
L2 Oil Temperature in °C
L3 Total hours run
L4 Hours run on-load
The display will reset to show delivery pressure 60
seconds after
VIEW
is last pressed.
1.6 Service Interval Timer
The controller uses a countdown timer which can
be reset to programmed maximum each time a
service is carried out. The maximum reset hours
can be adjusted to suit site conditions and/or
service schedule requirements. When the timer
reaches zero hours, indicator L3 will slow flash to
indicate a service is due. When the service has
been completed the service countdown timer can
be reset by entering the program mode, selecting
the service interval hours display (indicator L3),
and pressing
STOP
. The service interval
countdown timer will reset to the hours displayed
on the program mode service interval setting. The
service due alarm can be reset by pressing
RESET
after the above procedure has been
completed.
The compressor must be stopped and the power
isolated to carry out the required service (see
'Safety Procedures'). On completion of the service
the service interval timer must be reset.
When in the normal running mode the 'hours
remaining until next service due' can be viewed at
any time. Press
VIEW
until indicator L3 is
illuminated and the display shows the total hours
run. Press and hold
PLUS
and the display will
show the hours remaining until the next service is
due until
PLUS
is released.