User manual

CompAir BroomWade Limited
page 40
2. PROGRAM MODE
2.1 Program Mode Routine
‘Program mode’ is used to access, view and/or
alter the operating parameters and options stored
in the memory of the controller.
1. To enter the ‘Program mode’ press
STOP
(B3) then press and hold
PLUS
(B4) and
MINUS
(B5) together.
2. After five seconds indicators L1 to L8 will
flash four times to indicate that the controller
has entered ‘Program mode’. Release
PLUS
and
MINUS
buttons when the indicators start
to flash.
3. After the indicators have flashed four times,
indicator L1 will remain lit and the display will
show the current upper pressure set point P1.
4. When
VIEW
(B1) is pressed indicator L1 will
extinguish and indicator L2 will light. The
display will now show the Oil temperature trip
setting.
5. Each time
VIEW
is pressed the next indicator
in the sequence L1 to L8 will light and the
display will show the appropriate option.
6. To alter a displayed setting, press
PLUS
(B4) or
MINUS
(B5) to adjust the displayed
value. The display will flash when an
adjustment is made. When the display
shows the required value, press
STOP
(B3)
to enter the new value in to the controller
memory. The display will show the new
setting as a steady value.
Note: Any adjustment that is not entered into the
controller memory by pressing
STOP
(B3) will be
ignored and the original value maintained.
7. Press
RESET
(B6) to return to normal
running mode.