Specifications

1-12
Compaq 3000 Series UPS Operation and Reference Guide
Compaq Confidential – Need to Know Required
Writer: Melinda Hill Puglisi Project: Compaq 3000 Series UPS Operation and Reference Guide Comments:
Part Number: 341251-002 File Name: b-ch1 Overview.doc Last Saved On: 8/26/99 2:39 PM
To shut down the entire network in the event of an emergency, the REPO ports
of multiple UPS units can be connected to a single switch.
IMPORTANT:
The REPO port meets the requirements of NFPA Articles 645-10 and
645-11 for a Disconnecting Means.
IMPORTANT:
If the remote switch is closed, the REPO feature shuts down protected devices
immediately and does not utilize the orderly shutdown procedure initiated by
Compaq Power Management Software.
The REPO feature shuts down UPS units operating under either utility or
battery power.
If the UPS was operating on battery power when the remote switch was closed, no
power will be available to the devices until utility power is restored.
Warranties
$25,000 Computer Load Protection Guarantee
To back up the wide range of features offered with the UPS, Compaq provides
a three-year limited warranty. In addition, Compaq offers a $25,000 Computer
Load Protection Guarantee (provided by the original equipment manufacturer).
IMPORTANT:
The warranty card supplied with the UPS must be filled in and returned to
qualify for the $25,000 Computer Load Protection Guarantee.
The $25,000 Computer Load Protection Guarantee only applies if:
The UPS is plugged into a suitably grounded and wired outlet using no
extension cords, adapters, other ground wires, or other electrical
connections.
The UPS installation complies with all applicable electrical and safety
codes specified by the National Electrical Code (NEC).
The UPS is used under normal operating conditions. Users comply with
all instructions and labels.
The UPS is not damaged by accident (other than a utility power
transient), misuse, or abuse.