Part Number: 341251-002 File Name: j-appc Specifications.doc Last Saved On: 8/26/99 2:44 PM
Battery Runtime
Table C-7
Estimated Battery Runtime
Load (VA) Battery Runtime (Minutes)
700 80
800 56
900 50
1000 45
1200 38
1400 32
1500 30
1800 21
2000 19
2200 17
2400 14
3000 11
If a device list the power in Watts, use the following conversion equation:
Volts x Amps = VA per device
If only Watts are given:
Watts x 1.35 = VA