NOTE:
NOTE:NOTE:
NOTE:
The SL Advanced Power Manager is an optional rack level solution for the HP
ProLiant SL6000 which enables server-level DC (or hardware) power on and off and
server-level monitoring. In addition, the SL APM will automatically discover SL
hardware components which are connected into the SL APM solution.
NOTE:
NOTE:NOTE:
NOTE:
The SL APM does not replace rack PDUs, but is designed to enable the
utilization of basic, low cost, rack PDUs while providing the functionality of 'switched'
PDUs which provide hardware power on/off of individual servers by turning off the AC
power to the power supplies of a given server. Because the SL servers share power
supplies to optimize power efficiency, using 'switched' PDUs to turn off the power
supplies in the chassis will result in the loss of all servers in that chassis. The SL APM
solves this by allowing server-level hardware power on/off of the DC power to the
individual server motherboards.
HP SL Advanced Power Manager Kit
538084-B21
HP SL Advanced Power Manager Distribution Module Kit
NOTE:
NOTE:NOTE:
NOTE:
Connects up to 10 chassis.
539264-B21
NOTE:
NOTE:NOTE:
NOTE:
Please see the UPS and PDU cable matrix's on the HP Power Protection and
Management page. Under Power Cords, click on the "HP Power Cord Matrix" link.
That link will list cable descriptions, requirements, and specifications for UPS and PDU
units. Please see the following link:
www.hp.com/products/powercords
.
HP Rack Series
HP Rack SeriesHP Rack Series
HP Rack Series
HP Rack 10000 G2 Series
HP Rack 10000 G2 SeriesHP Rack 10000 G2 Series
HP Rack 10000 G2 Series
(Carbon/Graphite Metallic)
HP 10642 G2 Pallet Universal Rack
AF001A
HP 10642 G2 Shock Universal Rack
AF002A
HP 10642 G2 1200mm deep Shock Rack
AF092A
HP 10647 G2 1200mm deep Shock Rack
AF094A
NOTE:
NOTE:NOTE:
NOTE:
It is mandatory to use a shock pallet when shipping racks with equipment
installed.
NOTE:
NOTE:NOTE:
NOTE:
Please see the QuickSpecs for Technical Specifications and additional
information:
http://h18000.www1.hp.com/products/quickspecs/12402_na/12402_na.html
NOTE:
NOTE:NOTE:
NOTE:
For additional information regarding Rack Cabinets, please see the following
URL:
http://www.hp.com/go/rackandpower
.
NOTE:
NOTE:NOTE:
NOTE:
The increasing power of new high-performance processor technology requires
increased cooling efficiency for rack-mounted servers. The 10000 G2 Series Racks
provide enhanced airflow for maximum cooling, allowing these racks to be fully
loaded with servers using the latest processors.
CAUTION:
CAUTION:CAUTION:
CAUTION:
If a third-party rack is used, observe the following additional requirements
to ensure adequate airflow and to prevent damage to the equipment: Front and rear
doors: If your 42U server rack includes closing front and rear doors, you must allow
830 square inches (5,350 sq cm) of hole evenly distributed from top to bottom to
permit adequate airflow (equivalent to the required 64 percent open area for
ventilation). Side: The clearance between the installed rack component and the side
panels of the rack must be a minimum of 2.75 inches (7 cm).
CAUTION:
CAUTION:CAUTION:
CAUTION:
Always use blanking panels to fill all remaining empty front panel U-
spaces in the rack. This arrangement ensures proper airflow. Using a rack without
blanking panels results in improper cooling that can lead to thermal damage.