Service manual
19 BUS fault  
05 
Keep Buzzing 
1.  Don’t let the UPS 
carry half-wave 
load, negative 
power load. Low PF 
inductive/capacitive 
load. 
2.  Don’t connect the 
UPS (inverter) 
output to the mains 
line. 
3. Check the BUS 
voltage measurement 
circuit. 
20 Over charger  
11 
Keep Buzzing 
1.  Check the battery 
Number. 
2.  Check the charging 
voltage 
measurement 
circuit. 
22 Line input site fault (L-N) 
09 
Once /2mins 
1.  Correct the wiring 
2.  Check the site-fault 
detection circuit 
3. Replace the global 
controller 
23 Battery / charger Fail 
13 
Once/s 
1.  Check the battery 
Number 
2. Check validation o
f
the BATTERY 
3.  Check the battery 
voltage 
measurement circuit
25 Fans fault 
10 
Once/s 
1.  Replace the Fans 
2. Check and repai
r
the fans detection 
circuit 
  Common Trouble Possible Cause And Solution 
  Transfer to Bypass Due to Output Overload 
Possible Cause: O/P load is larger than rated load in VA or in Wattage. 
Solution: Removed or reduce load connected to O/P socket. On line mode, the UPS will restart 
automatically. On battery mode, UPS must be OFF in advance and ON again. 
  Transfer to Bypass Due to Over-temperature   
Possible Cause 1:Ambient Temperature is higher than allowed operation temperature. 
Solution: Reduce ambient temperature or O/P load. 
Possible Cause 2: Thermal detection circuit failed. 
Solution: Refer to the thermal detection problem Solution on later pages. 
  Transfer to Bypass Due to DC Bus Over-voltage 
Possible Cause 1: Some non-fatal misbehavior of UPS. 
Solution: Turn off UPS and restart the UPS. 
Possible Cause 2: PFC circuit fails. 
Solution: Refer to PFC circuit failure analysis. 
29










