Service manual
6.3.1 Quick Start   
Before any detail check of UPS, please check the components listed in the following table. This 
action could help you find problem quickly and make following debug procedures go smoothly. 
Related Circuit Block Components to be checked Component Type  Fail condition 
BAT FUSE  1K/3K:F1/F2; 2K:F1  Fuse Open 
I/P FUSE (on PSDR)  F3,  Fuse  Open 
2K/3K:D16, D17, REC02 
1K:D10, D11, REC1
Diode  Short or open 
PFC converter 
2K/3K:Q09, 1K:Q14  IGBT  C-E short or open 
2K/3K:Q04, Q05, Q06, Q07 
1K:Q4, Q6, Q10Q11
MOSFET  D-S short or open 
Push-Pull Booster 
2K/3K:D05, D06, D07, D08
1K:D12, D13, D14, D15
Power Diode  Short or open 
Inverter 
2K/3K:Q13, Q14, Q15, Q16
1K:Q12, Q13
IGBT  C-E short or open 
Q2  MOSFET  D-S short or open 
Charger module 
D10, D11, D12, D13, D15
  Power Diode  Short or open 
Q201  MOSFET  D-S short or open 
SPS module 
D202, D203 Power Diode  Short or open 
!
If the fuse is open, replacing fuse only DOES NOT mean you have solved the problem. In 
most case, open of fuse is caused by other failure of components; therefore, before restart 
that UPS, you must find the real failure components and replace them! 
34