Service manual
P-11
06/2005
SET-UP AND CODE DESCRIPTION (CONTINUED)
FIGURE 4
Thermostat Setting Displayed cccc ccc cc c norn h hh hhh hhhh
Cut-in Temperature (F) 34º 35º 36º 37º 38º 39º 40º 41º 42º
Cut-out Temperature (F) 30º 31º 32º 33º 34º 35º 36º 37º 38º
Nominal Temperature (F) 32º 33º 34º 35º 36º 37º 38º 39º 40º
Nominal Temperature (C) 0 0.6 1.1 1.7 2.2 2.8 3.3 3.9 4.4
There are two submodes within the refrigeration mode that can be activated to achieve
energy conservation
The rst submode,
, refers to an optional evaporator fan relay. When X =
0 - the fan mode is disabled and the evaporator will turn on/off with the activation of
the compressor
1 - (Fan Mode 1) the evaporator fan will turn off 5 minutes after the compressor fan is
turned off
The second submode, , refers to the Periodic Defrost mode. If X =
0 - the periodic defrost mode is disabled
1 - the machine will defrost every 6 hours for 30 minutes - used in high humidity
environments .
Within the refrigeration mode, there is also a refrigeration conservation mode which raises
the cabinet temperature 18º F or 10º C during specied periods of time. Pressing selection
button two while any of the settings are displayed will enter you in to the refrigeration control
settings. Pressing selection button one will toggle you through the options. Pressing selec-
tion button three will exit this mode.