TRANSMITTAL 5995 Greenwood Plaza Blvd. Suite 100 Greenwood Village, CO 80111-4710 303-571-5377 303-629-7467 (fax) PROJECT: TO: ATTN: Ph/Fax: No.
3025 S. Parker Rd | Suite 1100 | Aurora | CO | 80014 (303)696-2602 | www.ssgroupinc.com SSG MEP, Inc. Date Received: December 4, 2012 ☒ REVIEWED ☐ REJECTED ☐ REVISE & RESUBMIT Submittal Number: 238126 Project Name: Northwestern Mutual-West Denver Office Building Project Number: 12J2000 Client/Construction Manager: Barker Rinker Seacat & Partners ☐ FURNISH WITH CHANGES NOTED ☐ RESUBMIT SPECIFIC ITEM(S) ☐ TRANSMITTED WITH NO REVIEW MADE Actions taken by SSG MEP, Inc.
TRANSMITTAL 5995 Greenwood Plaza Blvd. Suite 100 Greenwood Village, CO 80111-4710 303-571-5377 303-629-7467 (fax) PROJECT: TO: ATTN: Ph/Fax: No.
Submittal Stamp Sheet Project: Northwestern Mutual West Denver Office Bldg Project Address: 825 Simms Street, Lakewood CO Phipps’ Job #: 12J2000 Subcontractor / Supplier Specification Section Submittal No. Submitted For: Barker Rinker Seacat Architecture 3457 Ringsby Court, Suite 200 Denver CO 80216 Adams County Plumbing & Heating 238126 Split System Air Conditioners 238126.01, 02, 05, 06: FCU/ACCU-1 Product Data & Shop Drawings APPROVAL Gerald H. Phipps, Inc.
Carrier West 4800 Osage Street Denver, CO 80221 Ph: (303) 825-4328 Fax: (303) 820-2302 _______________________________________________________________________________________________ RE-SUBMITTAL COVER SHEET Northwestern Mutual Denver, Colorado Adams County Heating and Plumbing JOB: LOCATION: CONTRACTOR: TAG RTU-1 QTY 1 MODEL NUMBER 48A5T035FQV62AER FCU/ACCU-1 1 RAV-SP180KRT-UL RAV-SP180AT2-UL FCU/ACCU-2 1 MHWX-36-H-1 MKA-212 VAV 21 35ED DESCRIPTION Carrier 35 Ton R410A Variable Air Volume P
2669 E. Hwy 224•Denver, CO 80229•303 288 4546•FAX: 303 289 5756 DATE: November 9, 2012 JOB NO: PROJECT: GENERAL CONTRACTOR: ARCHITECT: MECH.
SUBMITTAL Performance Data Certified Dimension Print Model: RAV-SP180KRT-UL RAV-SP180AT2-UL 208/230 Volt – 1 Phase – 60 Hertz Qty: 1 Tagged: FCU/ACCU-1 Includes: Condensate Pump, Condensing Unit Pad, Low Ambient Standard to 5 Degrees (Wind Baffle Field Fabricated) Date: June 14, 2012
2.0"(50) 5.2"(132) Knock out system 12.6"(320) Air inlet Connecting pipe 13.4"(0.34m) 1/2"(12.7mm) 22.4"(568) Knock out system 2.0"(50) 9.0"(228) 5.9"(150) 1.9"(47) 2.9"(73.5) 2.9"(73.5) A B C Distance 0.9" (24) 8.5"(215) Center line 10.3"(262.5) Hanger 3.2" (82) 0.9"(26) Instrallation plate outline 6.0" 4.3" (153.5) (109) 0.9" (23) 5.2"(132) Remote controller holder 10.3"(262.5) Hanger 8.5"(215) 30.9"(786) 9.3"(235) 9.3"(235) Hanger Comments C 2.0"(50) or more 33.
SUPER DIGITAL INVERTER ENGINEERING DATABOOK 4. HIGH WALL TYPE 4-1. Specifications Piping Operating Range Controls Performance System ❚ Highwall USA Size Outdoor Model Indoor Model 018 RAV-SP180AT2-UL RAV-SP180KRT-UL 024 RAV-SP240AT2-UL RAV-SP240KRT-UL Cooling Rated Capacity (Btu/h) SEER 18000 19.5 25000 16.7 EER Heating Rated Capacity (Btu/h) 10.0 19000 9.1 26400 11.5 Convertible 23 9.
L1 L2 S BLK 5 5 CN67 (BLK) 31 OUTDOOR UNIT EARTH SCREW L1 L2 S OUTDOOR UNIT 12345 CN81(BLK) F301 FUSE T3.
0.8” (21) 21.7” (550) 0.2” (5) 19.1” (486) 2-Ø0.2” (6) hole R0.6” (15) 23.6” (600) 0.3” (8) Product external line Ø0.4” (11)×0.6” (14) U-shape hole Details of A legs 2.1” (54) 1.5” (38) 0.4” (11) 2” (51) 1.3” (32) 1.2” (30) 11.4” (290) Discharge guard 19.7” (500) 30.7” (780) 19.1” (486) 4.3” (108) B legs 2.4” (60) Details of B legs 23.6” (600) R0.6” (15) 2-Ø0.3” (6) hole Ø0.4” (11)×0.6” (14) U-shape hole Prpduct external line 1.5” (38) 2.1” (54) 23.6” (600) Drain hole(Ø1” (25)) 4.
SUPER DIGITAL INVERTER ENGINEERING DATABOOK 5-2. Wiring Diagram RAV-SP180AT2-UL ORN CN500 BRN P25 P24 P23 P22 P21 P20 YEL P35 P34 YEL YEL HP SW 3 3 P04 P05 P06 RED 1 1 WHI 2 2 BLK 3 3 1 1 CN300 Q200~205 IGBT Q300~305 MOS-FET R221 R321 R220 R320 R219 R319 L03 3 3 2 2 1 1 CN700 C13 CN603 P19 P18 F03 Fuse, T3.15A AC250V Power relay FM 6 4 3 2 1 PMV Pulse motor valve 3 3 2 1 1 TS (Suction pipe temp.
Submittal Stamp Sheet Project: Northwestern Mutual West Denver Office Bldg Project Address: 825 Simms Street, Lakewood CO Phipps’ Job #: 12J2000 Subcontractor / Supplier Specification Section Submittal No. Submitted For: Barker Rinker Seacat Architecture 3457 Ringsby Court, Suite 200 Denver CO 80216 Adams County Plumbing & Heating 238126 Split System Air Conditioners 238126.03, 04, 07, 08: FCU/ACCU-2 Product Data & Shop Drawings APPROVAL Gerald H. Phipps, Inc.
Carrier West 4800 Osage Street Denver, CO 80221 Ph: (303) 825-4328 Fax: (303) 820-2302 _______________________________________________________________________________________________ RE-SUBMITTAL COVER SHEET Northwestern Mutual Denver, Colorado Adams County Heating and Plumbing JOB: LOCATION: CONTRACTOR: TAG RTU-1 QTY 1 MODEL NUMBER 48A5T035FQV62AER FCU/ACCU-1 1 RAV-SP180KRT-UL RAV-SP180AT2-UL FCU/ACCU-2 1 MHWX-36-H-1 MKA-212 VAV 21 35ED DESCRIPTION Carrier 35 Ton R410A Variable Air Volume P
2669 E. Hwy 224•Denver, CO 80229•303 288 4546•FAX: 303 289 5756 DATE: November 9, 2012 JOB NO: PROJECT: GENERAL CONTRACTOR: ARCHITECT: MECH.
SUBMITTAL Performance Data Certified Dimension Print Model: MHWX-36-H-1 / MKA-212 208/230 Volt – 1 Phase – 60 Hertz Qty: 1 Tagged: FCU/ACCU-2 Includes: Low Ambient and Refrigeration Specialties Date: June 14, 2012
MHWX Direct Expansion Hi-Wall Fan Coil Direct Expansion Fan Coil 9,000 - 36,000 BTUH 344
HVAC Guide Specifications Direct Expansion Hi-Wall Fan Coil Nominal Size: 9,000 – 36,000 BTUH Multiaqua Model Number: MHWX-09 MHWX-12 MHWX-18 MHWX-24 MHWX-36 Part 1-General 1.01 System Description Multiaqua Direct Expansion Fan Coils are manufactured with high impact molded polymers. 1.02 Quality Assurance A. Certified in accordance with U.L. Standard 95, latest version (U.S.A.) B. Manufactured in a facility registered to ISO 9002, Manufacturing Quality Standard. C. Fully load tested at the factory. D.
G. Filters: 1. Unit shall contain 65% washable filters. Part 3-Controls and Safeties 3.01 Controls A. Fan coils shall be completely factory wired and tested. B. Shall be capable of heat pump operation. C. Controls shall include a circuit board, room sensor, indoor coil thermistor, transformer and wireless remote. D. Controls shall be capable of incorporating an optional hard-wired thermostat. 3.02 Safeties: A. Fan coil shall contain a non reusable fuse on the secondary voltage side of the transformer. B.
MHWX Product Specifications & Capacity Physical Data Model Number Height (in) Width (in) Depth (in) Weight (lbs) MHWX-09 MHWX-12 MHWX-18 MHWX-24 MHWX-36 11.70 12.00 14.20 14.20 14.40 34.60 39.00 46.10 46.10 57.10 7.10 7.10 8.10 8.10 8.50 20.00 22.00 35.60 37.40 54.
\ 349
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000-36,000 BTUH -------------------------------------- CAUTION -------------------------------------Care must be taken when handling sheet metal. Sheet metal parts have sharp edges and could cause injury. GENERAL Read the entire contents of this manual before beginning installation. Multiaqua assumes no responsibility for equipment installed contradictory to any code requirement or installation instructions.
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000-36,000 BTUH FAN COIL AND MOUNTING PLATE DIMENSIONS (in) Fan Coil Model Number A B C D E F G H I MHWX-09 MHWX-12 MHWX-18 MHWX-24 MHWX-36 34.6 39.0 46.0 46.0 57.1 11.7 12.0 14.2 14.2 14.4 7.5 7.5 3.8 3.8 4.0 7.5 7.5 3.8 3.8 4.0 3.5 3.6 6.1 6.1 6.1 2.7 2.7 2.4 2.4 2.8 1.6 1.5 2.4 2.4 1.5 0.8 1.1 1.7 1.7 1.7 1.8 1.7 2.4 2.4 1.5 J K Field Supplied Hole L Field Supplied Hole 0.8 1.0 1.8 1.8 1.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000 – 36,000 BTUH -------- CAUTION ------Care must be taken when handling sheet metal. Sheet metal parts have sharp edges and could cause injury. INSTRUCTIONS FOR INSTALLING THE MOUNTING PLATE Figure 3 1. After a suitable place for installation has been selected, place the mounting plate horizontally on the wall. Make sure the alignment is horizontal. Use a plumb line if available. Mark on the wall where the mounting holes will be drilled.
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000 – 36,000 BTUH INSTRUCTIONS FOR INSTALLING FAN COIL UNIT ONTO MOUNTING PLATE 1. Route the fan coil piping, electrical, condenser control wires and/or flexible drain hose through either of the 2.75” previously drilled holes in step 3 figure 4. Ensure that the piping is insulated per local and national codes. Improper insulation could result in voided warranty and/or building damage. Figure 6 Figure 6 2.
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000 – 36,000 BTUH INSTRUCTIONS FOR INSTALLING FAN COIL UNIT ONTO MOUNTING PLATE 4. Ensure that the drain tubing is installed with at least 1/4” per foot of downward slope. Figure 9 5. Secure the fan coil to the mounting plate by first sliding the fan coil onto the two notches provided on the mounting plate. Figure 9 & 10 6. Push the bottom of the fan coil towards the wall in order to engage the locking clips. Figure 11 7.
INSTALLATION & OPERATING MANUAL MHWW Hi-Wall Fan Coils 9,000 – 36,000 BTUH MHWX CONTROLS OPERATION GUIDE Wireless Control: Standard Control Package (Page 355) Optional Wired Control: EG-003 (Page 361) 355
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000 – 36,000 BTUH MHWX CONTROLS OPERATION GUIDE Wireless Control: Name and function of remote controller Note: x x x x x x Be sure there are no obstructions between receiver and remote controller. The remote control signal can be received at the distance of up to about 21 feet. Do not throw or drop the remote controller. Do not put any liquid in the remote controller and do not put it in direct sunlight or any place where it is very hot.
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000 – 36,000 BTUH MHWX CONTROLS OPERATION GUIDE FUNCTION 1. TRANSMISSION SOURCE - Infra red transmission source 2. POWER - Press to turn the fan coil on and off or vice versa. (Red LED left will light to indicate the control is on) 3. MODE - To select desired operation mode. It will switch from one to another as shown. COOL - Cooling operation. DRY - Humidity control. HEAT - Heating operation. FAN - Fan only. No cooling or heating capability.
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000 – 36,000 BTUH MHWX CONTROLS OPERATION GUIDE FUNCTION 5. TEMPERATURE SETTING - Press “Ÿ” to increase set temperature. - Press “ź” to decrease set temperature. - Press “Ÿ” and “ź” Simultaneously to toggle between °C and °F display mode. - Temperature range: 16 C to 30°C in °C display mode and 60°F to 86°F in °F display mode. 6. DELAY TIMER SETTING - The delay timer is capable of delaying both on and off functions.
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000 – 36,000 BTUH MHWX CONTROLS OPERATION GUIDE 7. 8. CANCEL - To cancel any setting on the delay timer. LOUVER - Two different functions are available: 1. To set the louver stop position. There are 4 angles available. The sequence is as follows. 2. To set the louver swing (continuous motion). The sequence is as follows. 9. SLEEP - This function when selected will allow the user to determine a “sleep” period.
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000 – 36,000 BTUH MHWX CONTROLS OPERATION GUIDE 11. AUTO - This function will automatically control the system switching between heating and cooling operation. If the present auto mode is cooling, a switch to heating operation will begin only if the actual room temperature is 7° below selected control set point.
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000 – 36,000 BTUH MHWX CONTROLS OPERATION GUIDE Optional Wired Control: EG-003 LED MODE INDICATOR FOR REMOTE CONTROLLER: INDICATOR LIGHTS RED-GREEN RED-RED RED-BLINKING RED-OFF SETTING COOL HEAT AUTO FAN FUNCTION COOLING OPERATION ONLY HEATING OPERATION ONLY AUTO SELECTION BETWEEN HEAT & COOL FAN OPERATION ONLY 1. POWER - Press to turn the fan coil on and off or vice versa. 2. MODE - To select desired operation mode.
INSTALLATION & OPERATING MANUAL MHWX Hi-Wall Fan Coils 9,000 – 36,000 BTUH MHWX CONTROLS OPERATION GUIDE FUNCTION 4. TEMPERATURE SETTING - Press “Ÿ” to increase set temperature. - Press “ź” to decrease set temperature. - Press “Ÿ” and “ź” Simultaneously to toggle between °C and °F display mode. - Temperature range: 16 C to 30°C in °C display mode and 60°F to 86°F in °F display mode. 5. 6. CANCEL - To cancel any setting on the delay timer. LOUVER - Two different functions are available: 1.
MHWX-36-H-1 Wiring Diagram 208/230-1-50/60 366
MHWX CERTIFIED DRAWING 371
SUBMITTAL DATA MAXI KOOL-AIR COOLED CONDENSING UNIT COMPU-AIRE REFERENCE: EQUIPMENT MODEL: PA-5655-2 MKA-312 (C) DESCRIPTION: MAXI KOOL, Air Cooled Condensing DX Unit, Nominal 2 Ton, 2080V/1Ph/60 Hz with Control Panel wired to terminal block, Full control, programming and sequencing of unit shall be by others. The Unit shall consist of Condenser Coil, High Efficiency Scroll Compressor(s), and Condenser Blower-Motor Assembly. 1.
4.1 BLOWER MOTOR: The blower motor shall be Open Drip Proof, mounted on an adjustable base, provided with locking assembly to prevent motor play. The motor shall be 1725 RPM and shall have copper windings, phase isolation and shall be UL component recognized. 5.0 SCROLL COMPRESSOR: The unit shall utilize hermetically sealed high efficiency compressor(s). It shall employ an internal device to prevent reverse rotation upon shut down.
TECHNICAL DATA MAXI KOOL-AIR COOLED CONDENSING UNIT COMPU-AIRE REFERENCE: EQUIPMENT MODEL: PA-5655-2 MKA-312 (C) DESIGN AMBIENT TEMPRATURE 95°F DESIGN ALTITUDE (FT. ABOVE SEA LEVEL): 5,300 FT. No. of Ref. Circuits (Systems) 1 CONDENSER COIL CAPACITY: At 95°F Ambient Temperature @ 125°F CT, 40°F SST Sensible Heat Transfer Capacity-BTU/HR 30,078 CONDENSER COIL DATA-Aluminum Fins, 1/2" OD Copper tubing Face Area-Sq. Ft. 4.2 Rows/FPI 4/12 CONDENSER AIR FLOW DATA-Forward Curved Centrifugal Blower D.W.D.I.
MKA-3 (C) X