Manual

IO-Link Master 4-EIP User Guide: 2000582 Rev. A Chapter 5. IO-Link Port Configuration - 37
EtherNet/IP Settings Parameters
PDO Data Byte-Swap Method
Default: Word (16-bit) byte-swap
If enabled, the IO-Link Master swaps the data bytes in word (2 byte)
format or dword (4 byte) format. Supported values are:
No byte-swap – data passed through as received
Word (16-bit) byte-swap – data is byte-swapped in word format
Dword (32-bit) byte-swap – data is byte-swapped in dword format
Note: The byte swapping must be set correctly in order to convert from
EtherNet/IP (little-endian byte order), to IO-Link (big-endian byte
order).
Clear Event Code in PDO Block
Default: False
If enabled, the IO-Link Master expects the first 2 bytes, word, or dword of
the PDO block to be used for event code handling. Supported values are:
True = expect event code
False = no event code, expect only PDO data
Clear Event Code After Hold
Time
Default: True
If enabled, the IO-Link Master clears any event code reported in the PDI
data block after the Event Active Hold Time. Supported values are:
True = clear event code after hold time
False = do not clear event code after hold time
Event Active Hold Time
Default: 1000 ms
If Clear Event Code After Hold time is enabled, the time period an event
code is reported in the PDI block before it is cleared.
Valid range: 1-65535
Valid Units:
- ms (milliseconds)
- sec (seconds)
- min (minutes)
-hours
-days
Clear Event Hold Time
Default: 500 ms
Once an event code has been cleared, the time an event code stays cleared
in the PDI block before another event code can be reported.
Valid range: 1-65535
Valid Units:
- ms (milliseconds)
- sec (seconds)
- min (minutes)
-hours
-days
EtherNet/IP Settings Page (Continued)