Technical information
UGH024/1103 Portable Chillers
INSTALLATION
3-13
After the initial warm up, check for proper pump rotation. If
the pump rotation is correct, all other 3-phase components will
be in the proper rotation and do not need checked.
Manually turn on the pump from the main screen:
Press the arrow pointing to Run on the screen.
Manual Pump ON OFF
STATUS SETUP RUN ALM
Use the Scroll arrows to scroll through
Run screens to the Manual Pump screen.
Press the ON arrow.
The pump should begin running. Open the chiller cabinet
and check the rotation of the pump. The pump should be
turning clockwise. If the pump is not turning or is turning
counterclockwise, press the Stop Chiller button, discon-
nect the main power to the chiller and swap any two main
incoming wires. Reapply main power to the unit, scroll to
the Manual pump screen and again turn on the pump.
Pump should now be turning clockwise. If an alarm
occurs, see Answering Alarms, in the Troubleshooting
section. If alarm continues or reoccurs, call your Conair
Service representative.
Press the Escape/Previous Screen button.
The control returns to the main screen.
1
2
3
4
press arrow
press arrow
PLC C
ONTROL
CHECKING
THE
PUMP R
OTATION