20 Product Overview
3.4.2.2 OptiSorp steam distribution system
The OptiSorp steam distribution system is used in ventilation ducts with a short humidication distance
(for the calculation of the humidication distance refer to chapter 5.4.2). When ordering an OptiSorp
system the duct dimension must be specied. Please consult the data in the following table:
System 1 System 2 System 3 System 4
Number of
steam connector
1 2 3 4
Max. steam capacity 45 (30) kg/h 90 (60) kg/h 135 (90) kg/h 180 (120) kg/h
Duct width (B) 450...2700mm
Duct height (H) 450...1650 mm 450...2200 mm 800...3200 mm 800...3200 mm
* For duct widths <600 mm the value in brackets apply
Note: further information on the OptiSorp steam distribution system can be found in the separate manual
supplied with the OptiSorp steam distribution system.
H
B
H
B
H
B
H
B