Installation Instructions

20 Product Overview
3.4.2.2 OptiSorp steam distribution system
The OptiSorp steam distribution system is used in ventilation ducts with a short humidication distance
(for the calculation of the humidication distance refer to chapter 5.4.2). When ordering an OptiSorp
system the duct dimension must be specied. Please consult the data in the following table:
System 1 System 2 System 3 System 4
Number of
steam connector
1 2 3 4
Max. steam capacity 45 (30) kg/h 90 (60) kg/h 135 (90) kg/h 180 (120) kg/h
Duct width (B) 450...2700mm
Duct height (H) 450...1650 mm 450...2200 mm 800...3200 mm 800...3200 mm
* For duct widths <600 mm the value in brackets apply
Note: further information on the OptiSorp steam distribution system can be found in the separate manual
supplied with the OptiSorp steam distribution system.
H
B
H
B
H
B
H
B