Installation Instructions

26 Mounting and installation work
Typical installation for room humidication
Fig. 8: Typical installation for room humidication
Z261
KS10
DS80
BP
BP
Humidity sensor or
humidity controller
Steam line
As short as possible (max. length 4 m)
Adequate upslope/downslope min.15 % (8.5°)
No restrictions
Condensate trap at the lowest point
Hose or xed pipe (with same inner diameter
as steam outlet)
Blower Pack
(mounted separated from the steam humidier)
Condsensate line
– Min. downslope 15 % (8.5°)
– No restrictions
– Condensate trap ømin 200 mm
Filter valve or
Shut-off valve and lter 5µm
Water drain connector ø30 mm
Water supply connector G 3/4"
Water supply pipe
(min. inner diameter 8 mm, supplied by others)
1...10 bar / 1...40 °C
(with optional drain water
cooling 2...10 bar / 1...25 °C)
Electrical isolator heating voltage supply
(supplied by others)
ømin: 40 mm
Electrical isolator control voltage
supply (supplied by others)
Drain hose (supplied)
internal diameter ø30 mm
Drain hose must be led to the left
constant downslope (min 15 %/8.5°) to funnel
if using DI or RO water, use supplied drain hose or stainless
steel pipe only
must not touch funnel
Open funnel with trap
(supplied by others)
High limit humidistat
(external safety chain)
to drain *
to cylinder *
* connector used with remote
blower pack mounting only
ømin : 200 mm