Installation Instructions

35Mounting and installation work
5.4 Steam installation
5.4.1 Overview steam installation for duct humidication
Fig. 14: Overview steam installation for duct humidication
KS10
DS80
DV81
Steam line
As short as possible (max. length 4 m)
Adequate upslope/downslope min.15 % (8.5°)
No restrictions
Condensate trap at the lowest point
Hose or xed pipe (with same inner diameter as
steam outlet)
Condsensate line
– Min. downslope 15 % (8.5°)
– No restrictions
– Condensate trap ømin 200 mm
ømin: 200 mm
Calculated absorption distance B
N
to any obstruction
or min. 2.4 ... 3 m if B
N
is unknown
min. 3 m
min. 300 mm
min. 300 mm
Pmax 1500 Pa
Pmin -1000 Pa
Rmin:
300 mm
to drain
to cylinder
Supply duct