Installation Instructions

38 Mounting and installation work
Example
given
φ1= 30 %rh, φ2= 70 %rh
absorption distance B
N
:
1,4 m
(0.36 m for steam distribution system OptiSorp)
Note: If the absorption distance has to be reduced for technical reasons, the amount of steam per unit
must be divided between several steam distribution pipes or the steam distribution system OptiSorp
must be used. If this is the case, contact your Condair representative.
Minimum distances to be observed
To prevent the steam, that is emitting from the steam distributor, from condensing on downstream system
components, a minimum distance to the steam distributor must be observed (depends on the absorp-
tion distance "B
N
").
before/after constriction after expansion
0.5 x B
N
(1.97")
50 mm
0.5 x B
N
before bend before branch
1 x B
N
1 x B
N