Installation Instructions

40 Mounting and installation work
Installation notes
The steam distribution pipes are designed for either horizontal installation (on the duct wall) or, with ac-
cessories, for vertical installation (in the duct oor). The outlet orices should always point upwards
and at right angles to the airow.
If possible, the steam distribution pipes should be installed on the pressure side of the duct (max.
duct pressure 1500 Pa). If the steam distribution pipes are installed on the suction side of the duct, the
maximum vacuum must not exceed 1000 Pa.
Select a location for the installation, tailored to suit your duct (see the following illustrations) and position
the steam distribution pipes in the duct so that a uniform distribution of steam is achieved.
Positioning the steam distribution pipes in the duct
In positioning the steam distribution pipes, the following dimensions should be observed:
H
1/3
2/3
h
min
H min.= 250 mm
h min.= 85 mm
H
1/2
1/2
H ≥400 mm
H
1/2
1/2
H min.= 200 mm
H min.= 400 mm
H
2/7
2/7
3/7
H min.= 350 mm
g min.= 150 mm
H
2/7
2/7
3/7
g
min
H min.= 300 mm
H
1/3
1/3
1/3