43Mounting and installation work
5.4.4 Positioning and mounting of the blower packs (accessory BP)
The blower packs can either be mounted directly on the humidier or separately above the humidier
to the wall. To allow the steam coming from the blower pack to spread out evenly, without condensing
on obstacles (ceilings, joists, pillars, etc.), the following minimum dimensions must be observed when
selecting the location for the blower pack.
Fan speed: low Fan speed: high
Steam capacity humidier kg/h 5...10 >10...20 >20...30 >30...40 5...10 >10...20 >20...30 >30...40
A min. m 2.5 5.5 8.0 9.5 2.0 3.0 4.5 6.5
B min. m 0.5 0.5 0.5 1.5 0.5 0.5 0.5 1.0
C min. m 2.2
D min. m 0.5
E min. m 1.0
E max. m 4.0 (recommended: 2.0)
Note: The minimum spaces in the table apply for a room atmosphere of 15 °C and 60 %rh. For lower
temperatures and/or higher humidity the values should be adjusted accordingly.
Note: In order to achieve a uniform distribution of the humidity within the room, additional factors such as
the room size, the room height, etc., must be taken into consideration besides observing the minimum
distances for the blower packs. If you have questions concerning the direct room humidication, please
contact your Condair representative.
Further information is provided in the separate installation and operating instructions for the correspond-
ing blower pack.