Installation Instructions

50 Mounting and installation work
5.5 Water installation
5.5.1 Overview water installation
Fig. 21: Overview water installation for single units Small ("S") and Medium ("M")
Fig. 22: Overview water installation for single units Large ("L")
Filter valve or
Shut-off valve and lter 5µm
Water drain connector ø30 mm
Water supply connector G 3/4"
Water supply pipe
(min. inner diameter 8 mm, supplied by others)
Drain hose (supplied)
internal diameter ø30 mm
Drain hose must be led to the left
constant downslope (min 15 %/8.5°) to funnel
must not touch funnel
if using DI or RO water, use supplied drain hose or stainless
steel pipe only
Open funnel with trap
(supplied by others)
ømin: 40 mm
1...10 bar / 1...40 °C
(with optional drain water
cooling 2...10 bar / 1...25 °C)
Filter valves or
Shut-off valves and lters 5µm
Water drain connectors ø30 mm
Water supply connectors G 3/4"
Water supply pipes
(min. inner diameter 8 mm,
supplied by others)
Drain hoses (supplied)
internal diameter ø30 mm
Drain hoses must be led to the left
constant downslope (min 15 %/8.5°) to funnel
must not touch funnel
if using DI or RO water, use supplied drain hoses or stainless
steel pipes only
Open funnels with trap
(supplied by others)
ømin: 40 mm
1...10 bar / 1...40 °C
(with optional drain water
cooling 2...10 bar / 1...25 °C)