Installation Instructions

51Mounting and installation work
Fig. 23: Overview water installation for double units Medium ("M ")
Filter valves (accessory) or
Shut-off valves and lters 5µm
Water drain connectors ø30 mm
Water supply connectors G 3/4"
Water supply pipes
(min. inner diameter 8 mm, supplied by others)
Drain hoses (supplied)
internal diameter ø30 mm
Drain hoses must be led to the left
constant downslope (min 15 %/8.5°) to collector pipe
Fix drain hoses with hose clamp to the hose connectors
of the collector pipe
if using DI or RO water, use supplied drain hose or
stainless steel pipe only
Collector with hose connectors (ø30 mm) and drain pipe
(not supplied)
Internal diameter drain pipe min. ø60 mm
constant downslope (min 15 %/8.5°) to funnel
Drain pipe of collector must not touch funnel
if using DI or RO water, the collector pipe must be made
of stainless steel
Open funnel with trap
(supplied by others)
1...10 bar / 1...40 °C
(with optional drain water
cooling 2...10 bar / 1...25 °C)
ømin: 60 mm