Installation Instructions

9Product Overview
3 Product Overview
3.1 Models overview
Condair RS steam humidiers are available as single units with different housing sizes (S, M and
L), as double units (2 x "M") and as Linkup systems (3 x "M" or 4 x "M") with different heating
voltages and steam capacities ranging from 5 kg/h up to a maximum of 160 kg/h.
3.1.1 Single units Small ("S") , RS 5...10 and Medium ("M"), RS 16...40
Housing
size
Condair 230 V/1~ 200V/3~ 230V/3~ 380V/3~ 400V/3~ 415V/3~ 440V/3~ 460V/3~ 480V/3~ 500V/3~ 600V/3~
kg/h kg/h kg/h kg/h kg/h kg/h kg/h kg/h kg/h kg/h kg/h
S
RS 5 5.0 –– 5.0 4.6 5.0 5.4 –– –– –– –– ––
RS 8 8.0 –– 8.0 7.3 8.0 8.7 –– –– –– –– ––
RS 10 9.8 –– 9.8 9.0 10.0 10.7 10.8 11.8 12.8 13.9 10.3
M
RS 16 –– 14.9 16.0 14.5 16.0 17.3 15.3 16.7 18.2 19.8 14.2
RS 20 –– 18.1 19.7 17.9 20.0 21.4 17.2 18.8 20.5 22.2 21.3
RS 24 –– 22.3 24.0 21.8 24.0 26.0 –– –– –– –– ––
RS 30 –– 30.0 29.5 26.9 30.0 32.0 24.0 26.2 28.6 31.0 32.0
RS 40 –– –– –– 36.1 40.0 43.1 36.0 39.4 42.9 46.5 42.7
Fig. 1: Overview single units Small ("S") and Medium ("M")
I/O
Driver board
Module A
Control
board
RFI
Heating voltage
Module A
Control voltage
Control signal
External enable
Limiter signal
Safety chain
Remote indication
Main
Module A