2580644-A EN 1610 OPERATION MANUAL Steam humidifier Condair RS Humidification and Evaporative Cooling
Thank you for choosing Condair Installation date (MM/DD/YYYY): Commissioning date (MM/DD/YYYY): Site: Model: Serial number: Manufacturer Condair Operations GmbH Schnackenburgallee 43-45 DE - 22525 Hamburg Phone +49 40 52 47 266 16, Fax +49 40 52 47 266 30 info@condair.com, www.condair.com Proprietary Notice This document and the information disclosed herein are proprietary data of Condair Group AG.
Contents 1 Introduction 5 1.1 To the very beginning 5 1.2 Notes on the operation manual 5 2 For your safety 7 3 Product Overview 9 3.1 Construction Condair RS steam humidifier 9 3.2 Functional description 10 3.3 System overview Condair RS for duct humidification 11 3.4 System overview Condair RS for direct room humidification 12 4 Operation 13 4.1 First-time commissioning 13 4.2 Display and operating elements 13 4.
6 Maintenance 50 6.1 Important notes on maintenance 50 6.2 Maintenance intervals 51 6.3 Maintenance list 52 6.4 6.4.1 6.4.2 6.4.3 6.4.4 6.4.5 6.4.6 6.4.7 6.4.
1 Introduction 1.1 To the very beginning We thank you for having purchased the Condair RS steam humidifier. The Condair RS steam humidifier incorporates the latest technical advances and meets all recognized safety standards. Nevertheless, improper use of the Condair RS steam humidifier may result in danger to the user or third parties and/or damage to property.
Symbols used in this manual CAUTION! The catchword "CAUTION" used in conjunction with the caution symbol in the circle designates notes in this operation manual that, if neglected, may cause damage and/or malfunction of the unit or damage to property. WARNING! The catchword "WARNING" used in conjunction with the general caution symbol designates safety and danger notes in this operation manual that, if neglected, may cause injury to persons.
2 For your safety General Every person working with the Condair RS must have read and understood the Condair RS operation manual before carrying out any work. Knowing and understanding the contents of the operation manual is a basic requirement for protecting personnel against any kind of danger, to prevent faulty operation, and to operate the Condair RS safely and correctly. All icons, signs and markings applied to the components of the Condair RS must be observed and kept in readable state.
Danger that may arise from the Condair RS steam humidifier DANGER! Danger of electric hazard! The Condair RS is mains powered. Live parts may be exposed when the unit is open. Touching live parts may cause severe injury or danger to life. Prevention: Before carrying out any work set the Condair RS out of operation as described in chapter 4.5 (switch off the unit, disconnect it from the mains and stop the water supply) and secure the unit against inadvertent power-up.
3 Product Overview 3.
3.2 Functional description The Condair RS steam humidifier is an atmospheric steam generator. It operates on the resistance heating principle and is designed for direct room air humidification (with blower pack) and indirect humidification (with steam distributor) in ventilating and air-conditioning systems. Water supply The water is supplied via a filter valve (accessory "Z261") to the steam humidifier. It reaches the steam cylinder via the level controlled inlet valve and the open filling cup.
3.
3.
4 Operation The Condair RS steam humidifier may be commissioned and operated only by persons familiar with the Condair RS steam humidifier and adequately qualified. It is the owner’s responsibility to verify proper qualification of the personnel. 4.1 First-time commissioning The first-time commissioning must always be done by a service technician of your Condair representative or a well trained and authorised person of the customer.
4.3 Commissioning after an interruption of operation The following description outlines the start up procedure after an interruption of operation (e.g. after servicing the steam humidifier). It is assumed that first-time commissioning has been carried out properly by the service technician of your Condair representative and the Condair has been configured accordingly. 1.
4.4 Notes on operation 4.4.1 Inspections during operation During operation the Condair RS and the humidification system have to be inspected weekly. On this occasion check the following: • the water and steam installation for any leakage. • the steam humidifier and the other system components for correct fixing and any damage. • the electric installation for any damage. If the inspection reveals any irregularities (e.g.
4.4.3 Draining of the steam cylinder To perform a draining of the steam cylinder proceed as follows: 1. Press on the button in the standard operating display. The "Manual" submenu appears. 2. In the "Manual" submenu press on the button of the cylinder(s) to be drained (, or ). Note: on single units button is shown only. 3. Press on the button to start the draining of the steam cylinder(s).
4.4.5 Performing a complete flushing of the Condair RO-A system Note: the FWA flushing function in the "manual" submenu appears only, if the Condair RS is connected to a Condair RO-A reverse osmosis system and if the reverse osmosis system was activated in the factory menu. To perform a complete flushing of the RO system proceed as follows: 1. Press on the button in the standard operating display. The "Manual" submenu appears. 2. Press on the button in the "Manual" submenu. 3.
5 Operating the control software 5.1 Standard operating display After switching on the Condair RS and the automatic system test the steam humidifier is in normal operating mode and the standard operating display is shown. Note: the appearance of the standard operating display depends on the current operating status and the configuration of the humidity control of the system and can deviate from the display shown below.
5.1.1 Operating status indication The following operation status indications may appear during operation: Operating status indications Description The control is initialising. The Condair RS is in standby mode (no demand present). The Condair RS performs a cylinder flushing. The Condair RS is producing steam (humidifying). The Condair RS checks the function of the level unit. The Condair RS is connected to a BMS, and the BMS has activated the diagnostic mode.
5.2 Navigating/Operating the control software Navigation element Action Accessing main menu Accessing system informations Performing manual steam cylinder draining Accessing help screen If you press on a field with a blue arrow symbol a new screen with additional informations or settings appears. This symbol on the left side of the operating status field and of the maintenance/malfunctions indication field indicates, that the system is working ok.
5.3 Information functions 5.3.1 Accessing support informations In the standard operating display press the button. The screen with the support information appears. 5.3.2 Accessing system informations In the standard operating display press the button. The system information screen appears. Use the arrow buttons to scroll up and down within the system information screens to access the different system information and operating data. General Tab – Humidifier Model: Product designation.
– Driver A.DB.A Version: Actual software version of the driver board of unit A (cylinder A). – Driver B.DB.A Version: Actual software version of the driver board of unit B (cylinder B). Note: this menu item appears only on double units or the large units with two steam cylinders. – Driver C.DB.A Version: Actual software version of the driver board of the Condair RO-A reverse osmosis system.
Service Tab – Operating hours: Total operating hours with humidity demand since initial commissioning of the system. – Operating hours A: Operating hours with humidity demand of cylinder A since initial commissioning. – Operating hours B: Operating hours with humidity demand of cylinder B since initial commissioning. Note: this menu item appears only on double units or the large units with two steam cylinders.
Features Tab – Manual Capacity A: Actual set capacity limitation in % of the maximum capacity. – Idle Mode: Actual set standby mode ("Idle Drain", "Keep Warm", "Standby"). – Softstart Mode: Actual status of the softstart function ("On" or "Off"). – Desalt: Actual status of the desalting function ("On" or "Off").
5.4 Configuration 5.4.1 Accessing the "Configuration" submenu Password: 8808 5.4.2 Activating/deactivating and configuration of options – "Features" submenu In the "Features" submenu you can determine different operating parameters of the Condair RS.
– Maintenance Extended: with this setting you determine the interval time in hours for the extended maintenance. dependent on the steam capacity 100 ...
– Inlet Correction: with this setting you determine the cycle ratio of the inlet valve in % of the standard setting value to balance out water pressure variations. Note: this menu item appears only with option "P" units with high control accuracy. Factory setting: Setting range: 100 % 50 ... 100 % Idle Mode Tab – Idle Mode: with this setting you determine the operational behaviour of the Condair RS in standby operation.
The following settings appear only, if "Idle Mode" is set to "Keep Warm". Note: If the keep warm function for standby operation is activated the temperature of the water in the steam cylinder is held on 60 °C (at 20 °C ambient temperature), so that the humidifier can produce steam as fast as possible as soon as a demand is present again.
Desalt Mode Tab – Desalt: with this setting you can activate ("On") or deactivate ("Off") the demineralisation mode. Factory setting: Options: Off On or Off Note: enable the demineralization mode if you are using softened water or water with a high conductivity. Note: if desalting mode is activated the steam cylinder is drained after the set foam detection counts (see following parameter "Water Desalt Counts") within an hour is reached. Thus preventing the formation of foam in the steam cylinder.
– Operation with timer controlled capacity limitation Activate the timer function (Capacity Timers: "On"). If the capacity timer is activated, up to eight switching points (Event 1... Event 8) with different capacity limits can be defined. Each switching point is defined by a weekday or weekday range, the switching time and the capacity limitation in % of the maximum capacity. Configuration notes: – the settings of an event remain active up to the next event.
– Op. Cycle limit: with this setting you determine whether the On/Off switching delay is set to optimise the lifetime of the heating contactors ("On") or whether the On/Off switching delay is reduced to optimise the precision of control ("Off" – reduced life of heating contactors). Note: This menu item appears only on units with normal control accuracy.
Accessory Board Tab Note: the "Accessory Board" tap with the corresponding settings appears only, if the optional accessory board (for the control of an external fan of the ventilation system or the optional valve for flushing the water supply line) is installed and activated in the factory level. – Fan On: with this setting you can activate ("On") or deactivate ("Off") the control of an external fan via the corresponding relay on the optional accessory board.
5.4.3 Humidity control Settings – "Control Settings" submenu In the "Control Settings" submenu you determine the control settings for the Condair RS steam humidifier. The control settings available depend on the selected signal source and the control mode as well as whether the steam humidifier is controlled with supply air limitation. Basic Tab – Source: with this setting you determine the source of the control signal.
– Signal Type Channel 1/3: with this setting you determine the control signal with which the steam humidifier is controlled. Note: this setting appears only if signal source is set to "Analog" and control mode is set to "Demand", "RH P" or "RH PI". Factory setting: Options: – 0-10 V 0-5V, 1-5V, 0-10V, 2-10V, 0-20V, 0-16V, 3.2-16V, 0-20mA, 4-20mA Signal Type Channel 2/4: with this setting you determine the limiter signal (supply air limitation) with which the steam humidifier is controlled.
– Operation with timer controlled capacity limitation Activate the timer function (Setpoint Timers: "On"). If the setpoint timer is activated, up to eight switching points (Event 1... Event 8) with different humidity setpoints can be defined. Each switching point is defined by a weekday or weekday range, the switching time and the humidity setpoint in %rh. Configuration notes: – the settings of an event remain active up to the next event.
– Band Channel 2: with this setting you set the proportional range for the internal P/PI supply air controller in %rh. Note: this setting appears only if the "Control Mode" is set to "RH P" or "RH PI" and "Control Channels" is set to "Dual". Factory setting: Setting range: – 15 % 6 ... 65 % Damp Channel 2: with this setting you set the time in seconds after which the supply air controller takes over the control of the demand signal.
Multi Unit Operation Tab – Linkup: with this setting you determine whether the unit is part of a Linkup system and acts as master or slave unit or whether the unit is not part of a Linkup system. Note: the master unit must be set always to "Main". The further slave units in the chain must be set in ascending order to "Ext1" to "Ext5". Factory setting: Options: – Linkup Units: with this setting you determine the number of units belonging to the linkup system. Factory setting: Setting range: – 1 1 ...
– Sequence Interval: with this setting you determine the interval time the control system compares the operating hours of the cylinders in order to change the starting order if sequential cylinder rotation activated. Note: this setting appears only, if the "Sequence Rotation" function is activated ("On").
– Contrast: with this setting you determine the desired value for the display contrast. Factory setting: Options: – Brightness: with this setting you determine the desired value for the display brightness. Factory setting: Options: – 8 1 (weak contrast) ... 31 (strong contrast) 52 1 (dark) ... 100 (white) LED Brightness: with this setting you determine the desired value for the brightness of the operation indication LED. Factory setting: Options: 52 1 (weak) ...
Network Parameters Tab The following network settings are used only for the communication via the integrated BACnet IP interface. – IP Type: with this setting you determine whether you want to assign the IP Address, the Subnet Mask, the Standard Gateway as well as the Primary and Secondary DNS address as fixed values or whether these should be dynamically assigned via a DHCP server.
Modbus Parameters Tab – Modbus: with this setting you can activate ("On") or deactivate ("Off") communication via a Modbus network. Note: in order to activate the setting of this parameter the Condair RS must be switched off and on again. Factory setting: Off Options: Off or On The following parameters appear only if the Modbus function is activated. – Modbus Address: with this setting you determine the Modbus address for the Condair RS for the communication via a Modbus network.
BACnet Parameters Tab – BACnet: with this setting you can activate ("MSTP" or "BACnet/IP") or deactivate ("Off") the communication via the integrated BACnet interface. Note: in order to activate the setting of this parameter the Condair RS must be switched off and on again.
The following settings appear only, if the parameter "BACnet" is set to "MSTP". Note: with BACnet MSTP the Condair RS acts as a slave node only device. – Parity: with this setting you set the parity bit for the data transfer. Factory setting: Options: – Even None, Even or Odd Baudrate: with this setting you set the Baudrate for the data transfer.
5.5 Maintenance functions 5.5.1 Accessing the "Service" submenu Password: 8808 5.5.2 Performing maintenance functions – "Service" submenu In the "Service" submenu you can reset the maintenance counters, access and save the fault and maintenance history and perform different diagnostic functions. General Service Tab 44 Operating the control software – Small Maint. Reset A: with the "Small Maint.
– RO Service Reset: with the "RO Service Reset" function you can reset the service message or the service counter, respectively for the maintenance of the RO systems. After pressing on the "RO Service Reset" button a confirmation window appears where the resetting must be confirmed. Note: this menu item appears only, if the Condair RS is connected to a Condair RO-A reverse osmosis system and if the reverse osmosis system was activated in the factory menu.
5.5.2.1 Input diagnostic functions – "Input Diagnostics" submenu The following input values can be viewed after accessing the "Input Diagnostics" submenu. Note: the input values can be accessed and viewed too, via the "Service Info" selection field in the standard operating display. Cylinder A Tab (Cylinder B Tab) Note: the tabs of the input diagnostics for Cylinder B appear only on double units or large units with two steam cylinders.
– 24V External Supply: Actual voltage of the external 24 V supply. – 10V External Supply: Actual voltage of the external 10 V supply. RO Tab The "RO Tab" appears only, if the Condair RS is connected to a Condair RO-A reverse osmosis system and if the reverse osmosis system was activated in the factory menu. – PS1: Actual inlet pressure of the pump of the reverse osmosis system in bar. – PS2: Actual pressure in the pressure tank of the reverse osmosis system in bar.
5.5.2.2 Relay diagnostic functions – "Relay Diagnostics" submenu Remote Fault board Tab – Running: with this function you can activate ("On") and deactivate ("Off") the relay "Steam" on the remote operation and fault indication board. – Service: with this function you can activate ("On") and deactivate ("Off") the relay "Service" on the remote operation and fault indication board.
5.6.2 Switching on/off password protection and software updates function submenu "Administrator" In the "Administrator" submenu you can activate and deactivate the password protection for the main menu and the setpoint, and download software updates via a USB stick connected to the USB connector. Password settings Tab – Setpoint Password: with the function "Setpoint Password" you can protect the setpoint input screen with the user password "8808" against unauthorised access ("Yes") or not ("no").
6 Maintenance 6.1 Important notes on maintenance Qualification of personnel All maintenance work must be carried out only by well qualified and trained personnel authorised by the owner. It is the owner’s responsibility to verify proper qualification of the personnel. General note The instructions and details for maintenance work must be followed and upheld. Only the maintenance work described in this documentation may be carried out. Only use original Condair spare parts to replace faulty parts.
6.2 Maintenance intervals To maintain operational safety the Condair RS steam humidifier must be maintained at regular intervals. The control software of the Condair RS features two maintenance counters one for the "Small maintenance" (Cleaning of the scale collector tank, only for units equipped with a scale collector tank) and one for the "Extended maintenance" (Cleaning of the steam cylinder and othe components of the steam and water system).
6.3 Maintenance list Adjacent you can find an overview of the maintenance work to be carried out on "Small maintenance" and "Extended maintenance". Extended maintenance X X Remove and clean. X Remove, disassemble and clean, replace defective components if necessary. X Inspect, clean if necessary. X Remove, disassemble and clean, replace if necessary. Inlet valve X Remove and clean filter insert, replace if necessary. Filling cup X Inspect, clean if necessary.
6.4 Removing and installing components for maintenance 6.4.1 Preparing the Condair RS for the removal of components Before starting any removal work set the Condair RS out of operation and drain the steam cylinder and the scale collector tank (if applicable). Proceed as follows: 1. Condair RS must be switched on. Perform a draining of the steam cylinder (see chapter 4.4.3).
6.4.2 Removal and installation of the scale collector tank Removal WARNING! Danger of burning! Before removal of the scale collector tank ensure it is empty and the temperature indication adhesive on the scale collector tank indicates a temperature <122 °F (<50°C) . 1 2 Snap ring Strainer insert 2. 1. 1. 3. O-ring 4. 1. Press the latch of the spring-actuated lock at the scale collector tank to the top, then turn locking ring of the scale collector tank clockwise until it comes to a stop (1.).
Installation Prior to the installation: • Check scale collector tank, O-ring, snap ring and strainer insert for damages and replace defective components if necessary. We recommend to replace the sealings of the scale collector tank with each maintenance. For that purpose a maintenance kit is available (see parts list). • Remove any dirt inside the retaining ring on the bottom of the unit and clean it with a clean rag. 1 Snap ring Strainer insert 2 O-ring 4. 3. 2. 1. 1.
6.4.3 Removal and installation of the steam cylinder WARNING! Danger of burning! Before removal of the steam cylinder ensure the steam cylinder is empty and has cooled down, that no more burning danger exists. 1 2 1. Loosen retaining screw on front door on the steam cylinder side of the unit using a screwdriver, then remove the front door. 2. Free the upper hose clamp of the steam outlet hose using a screwdriver and pull the hose downwards from the steam connector.
3. Carefully lift the steam cylinder out of steam cylinder receptacle and remove it towards the front of the unit. CAUTION! Set down the steam cylinder carefully to ensure the funnel on the bottom side of the cylinder is not damaged! 4. Undo the steam cylinder cover clamping ring. 5 5. Carefully lift off the cover with the heating elements. CAUTION! Take care with the cover while it is removed, so as not to damage the heating elements.
6 7 6. If necessary, loosen the funnel insert by lightly rotating it in either direction and lift it together with baffle from the steam cylinder. Then, remove the screen insert from the funnel insert. 7. If during maintenance one or more heating elements must be replaced: 58 • First note position of the connecting cables inside the heating cable plug. • Then, loosen the corresponding cable inside the heating cable plug and remove.
Assembly and installation of the steam cylinder Assembly of the steam cylinder takes place in reverse sequence of the removal. Please note the following instructions: 6.4.4 – Installation of any heating elements which have been removed should follow the figure of step 7. Please take care that the heating elements are correctly positioned and the cables are correctly connected (according to your notes).
6.4.5 Removal and installation of the filling cup, the level unit and the water hoses For removing the filling cup, the level unit and the water hoses the steam cylinder must be removed first (see chapter 6.4.3). 1. Release hose clamps, then disconnect all hoses from the corresponding connectors and remove the hoses.
6.4.6 Removal and installation of the drain pump For removing the drain pump the steam cylinder must be removed first (see chapter 6.4.3). 2 1 3 4 1. Detach electric cables (polarity of the cables must not be observed). 2. Release hose clamps and remove the hoses from the connectors. 3. Undo the two screws on the bottom of the housing with Phillips screwdriver, then remove drain pump. 4.
6.4.7 Removal and installation of the inlet valve For removing the inlet valve the steam cylinder must be removed first (see chapter 6.4.3). 1 2 3 5 4 1. Detach electric cables (polarity of the cables must not be observed). Important: on multiple valves (units with increased control accuracy or units with option drain cooling) ensure to reconnect the connecting cables to same valve (note position). 2. Release hose clamp(s) and remove the hose(s) from the connector(s). 3.
6.4.8 Removal and installation of the steam cylinder receptacle For removing the steam cylinder receptacle the steam cylinder must be removed first (see chapter 6.4.3). A 4 2 1 3 B 5 1. Release hose clamps and remove hoses from the connectors. 2. Undo the screw fixing cylinder receptacle to the bottom of the housing with Phillips screwdriver. 3. Turn cylinder receptacle counterclockwise to the stop and remove cylinder receptacle upwards. 4. Remove snap ring and O-ring. 5.
6.5 Notes on cleaning the unit components Unit component What to clean and how to clean Scale collector tank • Dump any lime in scale collector tank, then carefully knock off any limescale inside scale collector tank and on the strainer insert. If the scale collector tank heavily calcified, fill scale collector tank with an 8% formic acid solution (observe safety notes in chapter 6.6), until the limescale comes off..
Unit component What to clean and how to clean Hoses • Remove any limescale by slightly knocking on the tubes using a rubber hammer. Then, rinse the tubes well with hot tap water. Inlet valve • Use a soft bristled brush (do not use a wire brush) to remove any limescale inside the inlet valve and on the strainer. • Wash inlet valve and strainer insert with a lukewarm soap solution, then rinse well with tap water.
Unit component What to clean and how to clean Drain cup • Use a soft bristled brush (do not use a wire brush) to remove any limescale from the drain cup and its connectors. If the drain cup is heavily calcified, place it in an 8% formic acid solution (observe safety notes in chapter 6.6), until the limescale comes off. • Wash the drain cup and the receptacle on the bottom side of the unit with a lukewarm soap solution, rinse the parts well with tap water.
6.7 Resetting the maintenance counter After completing the "Small maintenance" or the "Extended maintenance", the corresponding maintenance indication or maintenance counter (for module A or module B or for both), respectively must be reset. Proceed as follows to reset the maintenance counter: 1. Select in the "Service" submenu the corresponding reset function. Password: 8808 2. The reset dialogue appears: • Press the button to reset the corresponding maintenance counter.
6.8 Performing software and firmware updates To update the control software or the driver board firmware, proceed as follows: 1. Set the On/Off switch on the front side of the steam humidifier to the Off position, then switch off the voltage supply to the steam humidifier via the external disconnect switch (electrical isolator) and secure switch in the off position to prevent it from inadvertent power up. 2. Unlock the door panel on the control compartment side of the steam humidifier and remove it. 3.
7 Fault elimination 7.1 Important notes on fault elimination Qualification of personnel Repair work must be carried out only by qualified and well trained professionals authorised by the owner. Repair work relating to the electrical installation must be carried out by an electrician or professionals authorised by the owner. General notes Only use original spare parts from your Condair representative to replace defective parts.
Fault Operational states where further operation is not possible, or where further operation would damage the system are indicated with a fault message, additionally the fault indicator LED below the touch panel will lights up red. If such a malfunction occurs, the steam production of the Condair RS will be stopped automatically. By pressing on the maintenance and malfunction indication field in the standard operating display the error list shown with all active warning and fault messages.
Code Message Warning Fault ––– E22 ––– E26 ** Information Possible causes Max. Filling Time Contactor Jammed Water feed blocked, shut-off valve in the water supply line closed, filter valve closed or blocked). Water pressure too low. Check water feed (filter, pipes, etc.), check/open shut-off valve, Check water pressure. Inlet valve blocked or defective. Check strainer inside the inlet valve, clean if necessary. Replace valve.
Code Message Warning Fault ––– E47 ––– E52 ** Information Possible causes Invalid Level Unstable Level Magnetic field in vicinity of level unit. Eliminate magnetic field. Level unit defective. Replace level unit Unstable level detected, humidification is stopped Check hose connections between level unit and steam cylinder receptacle and between level unit and steam outlet hose. ––– E56 Int.
Code Message Warning Fault ––– E95 ––– ––– ––– E97 ** E98 ** E100 ** Information Possible causes No Heating voltage Ext. 24V Supply Ext. 10V Supply IO Inlet 1 Main contactor defective. Let have the main contactor be checked/ replaced by an electrician Phase failure heating voltage supply. Check/switch on electrical isolator in the mains supply line. Let have fuses in the mains supply line be checked/replaced by an electrician. External 24 V supply faulty. Voltage too high or too low.
7.4 Saving fault and service histories to a USB memory stick The fault and service histories of the Condair RS can be saved to a USB memory stick for logging and further analysis. For this purpose proceed as follows: 1. Set the On/Off switch on the front side of the steam humidifier to the Off position, then switch off the voltage supply to the steam humidifier via the external disconnect switch (electrical isolator) and secure switch in the off position to prevent it from inadvertent power up. 2.
7.6 Replacing the fuses and backup battery in the control unit The fuses of the control unit must be replaced by authorized personnel only (e.g. electrician). Replace fuses of the control unit only with fuses matching the specifications below with the appropriate nominal current capacity . Never use refurbished fuses. Do not bridge the fuse holder. To replace the fuses or the backup battery proceed as follows: 1.
8 Taking out of service/Disposal 8.1 Taking out of service If the Condair RS must be replaced or if the Condair RS is not needed any more, proceed as follows: 1. Take the Condair RS out of operation as described in chapter 4.5. 2. Have the Condair RS (and if applicable othe system components) unmounted by a qualified service technician. 8.2 Disposal/Recycling Components not used any more must not be disposed of in the domestic waste.
9 Product specification 9.1 Performance data 200V/3~/50...60 Hz 230V/3~/50...60 Hz 380V/3~/50...60 Hz 400V/3~/50...60 Hz 415V/3~/50...60 Hz Max. steam capacity in kg/h PN max. in kW IN max. in A Cable cross section AL min. in mm2 Fuses "F3" in A, quick acting (gR) Max. steam capacity in kg/h PN max. in kW IN max. in A Cable cross section AL min. in mm2 Fuses "F3" in A, quick acting (gR) Max. steam capacity in kg/h PN max. in kW IN max. in A Cable cross section AL min.
9.2 Operating data Control accuracy – Standard unit ±5 %rh (with PI-control and use of untreated drinking water) ±2 %rh (with PI-control and use of de-ionized water) – Option P unit ±2 %rh (with PI-control and use of untreated drinking water) ±1 %rh (with PI-control and use of de-ionized water) Control steam output – active 0…5 VDC, 1…5 VDC, 0…10 VDC, 2…10 VDC, 0…20 VDC, 0…16 VDC, 3.2…16 VDC, 0…20 mADC, 4…20 mADC – passive all potentiometric humidity sensors from 140 Ω…10 kΩ – On/Off control <2.