Operation Manual

22 Operating the control software
Driver A.DB.A Version: Actual software version of the driver board of
unit A (cylinder A).
Driver B.DB.A Version: Actual software version of the driver board of
unit B (cylinder B).
Note: this menu item appears only on double units or the large units with
two steam cylinders.
Driver C.DB.A Version: Actual software version of the driver board of the
Condair RO-A reverse osmosis system.
Note: this menu item appears only, if the Condair RS is connected to a
Condair RO-A reverse osmosis system and if the reverse osmosis system
was activated in the factory menu.
Serial Number: Serial number of the steam humidier.
Graph: With this function you can access the graphical display of the
performance diagram of the Condair RS.
Export Trend Data: With this function you can save the data of the per-
formance diagram as .csv le to a USB memory stick (FAT32 formatted).
Note: before carrying this function, a FAT32 formatted USB memory stick
must be connected to the USB port on the control board.
Timer Cylinder A Tab
On/Off Timers: Actual status of the On/Off timer function ("On": On/Off
timer function activated, "Off": On/Off timer function deactivated).
Capacity Timers: Actual status of the timer controlled capacity limitation
function ("On": timer controlled capacity limitation activated, "Off": timer
controlled capacity limitation deactivated).
Setpoint Timers: Actual status of the setpoint timer function ("On": setpoint
timer function activated, "Off": setpoint timer function deactivated).