Operation Manual

25Operating the control software
5.4 Conguration
5.4.1 Accessingthe"Conguration"submenu
5.4.2 Activating/deactivatingandcongurationofoptions–"Features"submenu
In the "Features" submenu you can determine different operating parameters of the Condair RS.
Water Management Tab
Water Mode: with this setting you determine whether the ushing interval
time and the maintenance interval time for the small and the extended
maintenance are calculated automatically on the basis of parameters
water quality and water hardness (Setting: "Calculated") or whether the
ushing interval time and the maintenance interval time for the small and
the extended maintenance can be set manually (Setting: "Manual").
Factory setting: Manual
Options: Manual or Calculated
Water Reduction: with this setting you can activate ("On") or deactivate
("Off") the automatic water reduction function.
CAUTION: Deativating the water reduction function when using drink-
ing water can lead to heavy scaling of the steam cylinder!
Factory setting: On
Options: On or Off
The following settings appear only, if "Water Mode" is set to "Manual".
Note: The settings for the parameters to be selected depend on the supply
water quality and the steam capacity of the unit and must be set in ac-
cordance with the following table. It may have to be adapted to the actual
circumstances during operation.
Water Reduction Time: with this setting you determine the interval
time in minutes for the automatic ushing cycle.
Factory setting: dependent on the steam capacity
Setting range: 5 ... 720 minutes
Maintenance Small: with this setting you determine the interval time
in hours for the small maintenance.
Factory setting: dependent on the steam capacity
Setting range: 100 ... 3'000 h
Password: 8808