Operation Manual

27Operating the control software
Idle Mode Tab
Idle Mode: with this setting you determine the operational behaviour of
the Condair RS in standby operation.
Factory setting: Idle Drain
Options: Idle Drain (the steam cylinder is drained and re-
lled after a set time in standby operation)
Keep Warm (the water in the steam cylinder is
kept on a set temperature in standby operation)
Standby (Standby only without active function)
The following settings appear only, if "Idle Mode" is set to "Idle Drain".
Standstill Time: with this setting you determine, after which time in
the standby operation a level test is triggered.
Factory setting: 4 h
Setting range: 1 ... 72 h
Idle Drain Time: with this setting you determine, after which time in
the standby operation the steam cylinder(s) is/are completely drained
and relled again.
Factory setting: 24 h
Setting range: 1 ... 100 h
Inlet Correction: with this setting you determine the cycle ratio of the inlet
valve in % of the standard setting value to balance out water pressure
variations.
Note: this menu item appears only with option "P" units with high control
accuracy.
Factory setting: 100 %
Setting range: 50 ... 100 %