29Operating the control software
Desalt Mode Tab
– Desalt: with this setting you can activate ("On") or deactivate ("Off") the
demineralisation mode.
Factory setting: Off
Options: On or Off
Note: enable the demineralization mode if you are using softened water
or water with a high conductivity.
Note: if desalting mode is activated the steam cylinder is drained after
the set foam detection counts (see following parameter "Water Desalt
Counts") within an hour is reached. Thus preventing the formation of foam
in the steam cylinder.
The following setting appears only, if "Desalt" is set to "On".
– Water Desalt Counts: with this setting you determine how many times
the maximum level in the steam cylinder can be reached within on
hour (foam detection) before a time-controlled ushing cycle will be
initiated.
Factory setting: 3
Setting range: 1 ... 8
Operation Tab
– Manual Capacity A: with this button you can access the settings menu for
the capacity limitation. Here you determine whether the Condair RS is to
be operated with a x capacity limitation (factory setting) or whether it is
to be operated with a timer controlled capacity limitation.
Note: on large units with two steam cylinders and on double units the
capacity limitation is valid for both steam cylinders (A and B). On Linkup
systems the capacity limitation can be set for the main and the extension
units individually.
– Operation with xcapacitylimitation
Let the timer function deactivated (Capacity Timers: "Off") or deac-
tivate the timer function if necessary. Then, set the desired capacity
limitation of the steam humidier in % of the maximum capacity via
the "Manual Capacity A" parameter (Factory setting: 100 %, Setting
range: 20 ... 100 %).