Operation Manual
30 Operating the control software
– Operation with timer controlled capacity limitation
Activate the timer function (Capacity Timers: "On"). If the capacity
timer is activated, up to eight switching points (Event 1... Event 8)
with different capacity limits can be dened. Each switching point is
dened by a weekday or weekday range, the switching time and the
capacity limitation in % of the maximum capacity.
Conguration notes:
– the settings of an event remain active up to the next event.
– the software does not c heck the plausibility of the timer settings.
Therefore, make sure your settings make sense.
– the On/Off timer overrides the capacity limit timer.
– ON/Off Timers: with this button you can access the settings menu for the
On/Off timer.
With the "Timer" parameter you can activate ("On") or deactivate ("Off")
the On/Off timer.
If the timer is activated, up to eight switching points (Event 1... Event 8)
with different On/Off events can be dened. Each switching point is dened
by a weekday or weekday range, the switching time and the operating
mode of the steam cylinder.
Conguration notes:
– the settings of an event remain active up to the next event.
– the software does not check the plausibility of the timer settings.
Therefore, make sure your settings make sense.
– the On/Off timer overrides the capacity limit timers.