Operation Manual

34 Operating the control software
Setpoint Channel 1: with this button you can access the settings menu
for the humidity setpoint. Here you determine whether the Condair RS is
to be controlled with a x humidity setpoint (factory setting) or whether it
is to be operated timer controlled with different humidity setpoints.
Note: this menu item appears only if the "Control Mode" is set to "RH P"
or "RH PI".
Control with xhumiditysetpoint
Let the timer function deactivated (Setpoint Timers: "Off") or deactivate
the timer function if necessary. Then, set the desired humidity setpoint
value in %rF via the "Setpoint Channel 1" parameter (Factory setting:
40 %rh, Setting range: 5...95 %rh).
Signal Type Channel 1/3: with this setting you determine the control
signal with which the steam humidier is controlled.
Note: this setting appears only if signal source is set to "Analog" and
control mode is set to "Demand", "RH P" or "RH PI".
Factory setting: 0-10 V
Options: 0-5V, 1-5V, 0-10V, 2-10V, 0-20V, 0-16V, 3.2-16V,
0-20mA, 4-20mA
Signal Type Channel 2/4: with this setting you determine the limiter signal
(supply air limitation) with which the steam humidier is controlled.
Note: this setting appears only if signal source is set to "Analog", control
mode is set to "Demand", "RH P" or "RH PI" and Control Channels is set
to "Dual".
Factory setting: 0-10 V
Options: 0-5V, 1-5V, 0-10V, 2-10V, 0-20V, 0-16V, 3.2-16V,
0-20mA, 4-20mA
PI Control Parameters Tab