Operation Manual

36 Operating the control software
RH Alerts: with this setting you can activate ("On") or deactivate ("Off")
the output of a warning upon malfunction of the humidity sensor.
Factory setting: On
Options: On or Off
The following settings appear only if "RH Alerts" function is activated ("On").
RH High: with this setting you set the upper limit value in per cent
of the maximum signal value of the humidity sensor, if exceeded a
warning message is triggered.
Factory setting: 75 %
Setting range: 20 ... 95 %
RH Low: with this setting you set the lower limit value in per cent of
the maximum signal value of the humidity sensor, if undershooted a
warning message is triggered.
Factory setting: 20 %
Setting range: 20 ... 95 %
Sensor Min: with this setting you set the minimum signal value in per
cent of the maximum signal value of the humidity sensor, if undershot
a sensor interruption message is triggered.
Factory setting: 5 %
Setting range: 1 ... 10 %
Enable Input: With this setting you determine wether the Condair RS
can be enabled and disabled via an external enable contact ("On") or not
("Off").
Factory setting: On
Options: On or Off
RH Alerts Tab
Note: The "RH Alerts" settings appear only, if the internal P or PI controller is activated.
Band Channel 2: with this setting you set the proportional range for the
internal P/PI supply air controller in %rh.
Note: this setting appears only if the "Control Mode" is set to "RH P" or
"RH PI" and "Control Channels" is set to "Dual".
Factory setting: 15 %
Setting range: 6 ... 65 %
Damp Channel 2: with this setting you set the time in seconds after which
the supply air controller takes over the control of the demand signal.
Note: this setting appears only if the "Control Mode" is set to "RH P" or
"RH PI" and "Control Channels" is set to "Dual".
Factory setting: 5 seconds
Setting range: 1 ... 60 seconds