Operation Manual
37Operating the control software
Multi Unit Operation Tab
– Linkup: with this setting you determine whether the unit is part of a Linkup
system and acts as master or slave unit or whether the unit is not part of
a Linkup system.
Note: the master unit must be set always to "Main". The further slave units
in the chain must be set in ascending order to "Ext1" to "Ext5".
Factory setting: Off
Options: Off (no Linkup system)
Main (Master unit of the Linkup system)
Ext1 (rst slave unit of the Linkup system)
Ext2 (second slave unit of the Linkup system)
Ext3 (third slave unit of the Linkup system)
Ext4 (fourth slave unit of the Linkup system)
Ext5 (fth slave unit of the Linkup system)
– Linkup Units: with this setting you determine the number of units belong-
ing to the linkup system.
Factory setting: 1
Setting range: 1 ... 6
– Linkup Type: With this setting you determine how the demanded capacity
is to be divided on the individual units of the linkup system.
Factory setting: Parallel
Options: Parallel (even distribution of the demand on the units)
Series (serial distribution, rst Main up to 100 %, the
up to 100 %, etc.)
Independent (the units of the linkup system are
working independently)
– Sequence Rotation: with this setting you determine whether the cylinder
with the lowest number of operating hours is started rst ("On") or not
("Off") if serial distribution of the demand is activated
Note: this setting appears only, if "Linkup Type" is set to "Series".
Factory setting: On
Options: On or Off