Operation Manual
38 Operating the control software
– Sequence Interval: with this setting you determine the interval time the
control system compares the operating hours of the cylinders in order to
change the starting order if sequential cylinder rotation activated.
Note: this setting appears only, if the "Sequence Rotation" function is
activated ("On").
Factory setting: 24 hours
Setting range: 24 ... 1000 hours
– Linkup Timeout: with this setting you determine, how long the units of a
linkup systems can operate without connection among each other, before
an error message is triggered.
Note: this setting appears only on the "Main" unit of a linkup system.
Factory setting: 60 seconds
Setting range: 60 ... 120 seconds
– Zero Out A: this parameter indicates at which percentage of the demand
signal cylinder A is switched on (calculated value).
– Full Out A: this parameter indicates at which percentage of the demand
signal cylinder A is switched off (calculated value).
– Zero Out B: this parameter indicates at which percentage of the demand
signal cylinder B is switched on (calculated value).
– Full Out B: this parameter indicates at which percentage of the demand
signal cylinder B is switched off (calculated value).
5.4.4 Basicsettings–"General"submenu
In the "General" submenu you determine the basic settings for operating the Condair RS control software.
Basic Tab
– Date: with this setting you determine the current date in the set format
("MM/DD/YYYY" or "DD/MM/YYYY").
Factory setting: 00/00/0000
– Time: with this setting you set the current hour of the day in the set time
format ("12H" or "24H", see Time/Date Tab below).
Factory setting: 12:00
– Language: with this setting you determine the dialogue language.
Factory setting: depending on the country
Options: various dialogue languages
– Units: with this setting you determine the desired unit system.
Factory setting: depending on the country
Options: Metric or Imperial