40 Operating the control software
Network Parameters Tab
The following network settings are used only for the communication via the
integrated BACnet IP interface.
– IP Type: with this setting you determine whether you want to assign the IP
Address, the Subnet Mask, the Standard Gateway as well as the Primary
and Secondary DNS address as xed values or whether these should be
dynamically assigned via a DHCP server.
Note: after 5 unsuccessful attempts at obtaining an address with DHCP
the system will revert to xed assignment
Factory setting: DHCP
Options: DHCP (dynamic assignment)
Fixed (xed assignment)
– IP Address: with this setting you manually enter the IP Address of the
Condair RS.
Note: This IP Address is used if "IP Type" is set (or reverts) to "Fixed".
– Subnet Mask: with this setting you determine the Subnet Mask of the IP
network.
Note: This Subnet Mask is used if "IP Type" is set (or reverts) to "Fixed".
– Default Gateway: with this setting you determine the IP Address of the
Default Gateway.
Note: This IP Address for the Default Gateway is used if "IP Type" is set
(or reverts) to "Fixed".
– Primary DNS: with this setting you determine the IP Address of the Primary
Domain Name Server (DNS).
Note: This IP Address for the Primary Domain Name Server is used if "IP
Type" is set (or reverts) to "Fixed".
– Secondary DNS: with this setting you determine the IP Address of the
Secondary Domain Name Server (DNS).
Note: This IP Address for the Secondary Domain Name Server is used if
"IP Type" is set (or reverts) to "Fixed".
– MAC Address: factory set MAC Address (Media Access Control) of the
Condair RS. Not modiable.
– Host Name: Host Name of the Condair RS automatically generated by
the control. Format: "IC_"+"Serial number of the device". Not modiable.
BMS Timeout Tab
– BMS Timeout: with this setting you determine the maximum time the
humidier will wait with no communication from the BMS network before
a BMS timeout warning is generated. Exceeding the timeout also stops
humidier operation if the signal source of the humidier is set to a BMS
input.
Factory setting: 300 s
Setting range: 1 ... 300 s