Operation Manual
41Operating the control software
Modbus Parameters Tab
– Modbus: with this setting you can activate ("On") or deactivate ("Off")
communication via a Modbus network.
Note: in order to activate the setting of this parameter the Condair RS
must be switched off and on again.
Factory setting: Off
Options: Off or On
The following parameters appear only if the Modbus function is activated.
– Modbus Address: with this setting you determine the Modbus address
for the Condair RS for the communication via a Modbus network.
Factory setting: 10
Setting range: 1 ... 247
– Parity: with this setting you set the parity bit for the data transfer.
Factory setting: Even
Options: None, Even or Odd
– Baudrate: with this setting you set the Baudrate for the data transfer.
Factory setting: 9600
Options: 110, 300, 600, 1200, 2400, 4800, 9600, 19200,
38400, 57600, 76800 or 115200
– Register Sequence: with Modbus communication 32 Bit oating-point
numbers are transmitted in two registers of 16 Bit each. In order that
sender and receiver understand each other (that means both use the
identical partitioning of the 32 Bit to the two 16 Bit registers) it must be
determined whether the high-order register (MSR = Most Signicant
Register) or the low-order register (LSR = Least Signicant Register)
is transmitted rst. With this setting you determine which register is
transmitted rst when transmitting oating-point numbers.
Factory setting: LSRrst
Options: LSRrst(low-order register is transmitted rst)
MSRrst(high-order register is transmitted rst)