Operation Manual

78 Product specication
9.2 Operating data
Control accuracy
– Standard unit ±5 %rh (with PI-control and use of untreated drinking water)
±2 %rh (with PI-control and use of de-ionized water)
– Option P unit ±2 %rh (with PI-control and use of untreated drinking water)
±1 %rh (with PI-control and use of de-ionized water)
Control steam output
– active 0…5 VDC, 1…5 VDC, 0…10 VDC, 2…10 VDC, 0…20 VDC, 0…16 VDC,
3.2…16 VDC, 0…20 mADC, 4…20 mADC
– passive all potentiometric humidity sensors from 140 Ω…10 kΩ
– On/Off control <2.5 VDC --> Off; ≥2.5 VDC…20 VDC --> On
Duct air pressure
Overpressure max. 1500 Pa, Underpressure max. 1000 Pa
(for duct pressures outside these values contact your Condair representative)
Admissible ambient temperature 1...40 °C
Admissible ambient humidity 1...75 %rh (non-condensing)
Water supply
Admissible water supply pressure 1...10 bar (with optional drain water cooling 2...10 bar)
Admissible Feed temperature 1...40 °C (with optional drain water cooling 1...25 °C)
– Water quality Untreated drinking water, RO water, de-ionized water
(for operation with softened or partly softened water please contact your Condair repre-
sentative)
Water drain
– Drain water temperature 60...90 °C
Protection class IP21
9.3 Connections/Dimensions/Weights
Water supply connector G 3/4"
Water drain connector ø30 mm
Steam connector ø45.0 mm
Housing dimensions
– Small unit (S) - HxWxD 670 mm x 420 mm x 370 mm
– Medium unit (M) - HxWxD 780 mm x 530 mm x 406 mm
– Large unit (L) - HxWxD 780 mm x 1000 mm x 406 mm
Unit weights
– Small unit (S) - Net weight/operating weight 27.2 kg / 40.2 kg
– Medium unit (M) - Net weight/operating weight 40.3 kg / 65.8 kg
– Large unit (L) - Net weight/operating weight 81.0 kg / 132.0 kg
9.4 Certicates
Certicates CE, VDE