Technical data
  Learning units 
  3.9 9. Step: Configuration of the SINAMICS drive with S7T Config 
Sequence  Activity  Result 
24  Select parameter "p210" and enter "345". 
The smart line module and the motor module of the SINAMICS S120 training case have been especially 
equipped for operation on a 230 V system. For this reason, "Parameter p210" of the connected drives must 
be set to the following value, which differs from the factory settings: 
p210 = 345 V device connection voltage SERVO/VECTOR 
The setting of "parameter p210 = 345 V" 
cannot be calculated by the SINAMICS operating system and is 
pre-assigned for the error-free operation of the SINAMICS S120 training case on the 230 V system. 
CPU 317T-2 DP: Controlling a SINAMICS S120 
Getting Started, 12/2005, A5E00480391-01 
3-39 