Technical data
Technology functions 
  CPU 317T: Technology Functions 
6-212  A5E00251798-03 
Requirements for restart 
•  A restart is only possible when the relevant technology object is disabled, or 
not busy, or not in use by another application. 
Warning 
Set Restart = FALSE if you only want to clear the errors at a technology object. 
Re-initialization of a technology object (Restart = TRUE) may take several 100 
milliseconds. The technology object is not available for the duration of this process.
Overriding commands 
MC_Reset 
MC_Reset (Restart=FALSE) 
MC_Reset (Restart=FALSE)
MC_Home 
MC_ChangeDataset 
(Cancellation relationships are shown in read direction) 
An MC_Reset with Restart = TRUE can not be canceled 
Input parameters 
Parameter  Data type  Start value  Description 
Axis  INT  0  Number of the technology DB 
Execute  BOOL  FALSE  Start of the command at the positive edge 
Restart  BOOL  FALSE  FALSE: Acknowledge error 
TRUE: Restart - Re-initialization and application 
 of modified configuration parameters 