Technical data
  Technology functions 
CPU 317T: Technology Functions 
A5E00251798-03 
6-217 
ErrorID
Error message  Description / to correct or avoid error 
8052  Block call at different run levels  This block was called at different run levels using the 
same instance DB. 
Example: 
FBx is called in the instance DBx, in OB1, and in OB35. 
Execution of the FB started in OB1, and was interrupted 
by its call in OB35. Based on the shared use of the 
instance DB, the error is indicated at output parameter 
ErrorID of both FB calls. 
Error reactions to be expected: 
•  The new command (positive or negative edge at 
parameter input Execute/Enable) is not transferred to 
the integrated technology. 
•  The first command started can not be traced at the 
output parameter of the technology function. However, 
the command may still be active in the integrated 
technology. 
Warning: 
Use different instance DBs at different run levels, or 
interlock the call of the technology function. 
8053  Invalid instance DB  Faulty instance DB of the technology function (wrong 
length, for example.) 
8080  Invalid parameter number or 
parameter index 
The technology object does not support this parameter or 
parameter index.  
8083  DB is not a technology DB 
The DB specified at input parameter Axis or the 
technology DB were not found. 
8084 Invalid technology DB  •  A technology object does not exist in the PLC for the 
technology DB specified at input parameter Axis. 
Download the current technology to the PLC, or 
change the DB number at input parameter Axis. 
•  The user has written invalid data to the technology DB 
specified at input parameter Axis. 
In "Technology Objects Management", delete and then 
recreate the technology DB. 
8086  Parameter not available  Example: 
• 
Access to incremental encoder parameters in a system 
with absolute value encoders 
•  The technology object is currently performing a restart. 
It is therefore not possible to read the parameter. 