Technical data
  Technology functions 
CPU 317T: Technology Functions 
A5E00251798-03 
6-245 
Parameter Data 
type 
Start value  Description 
Data  ANY  --  Destination data area to which the parameter values 
should be saved. 
The maximum length of data to be read or transferred is 
defined by the data type and the repetition coefficient at 
the ANY pointer. 
The data area has a maximum size of 234 bytes. 
DoneFlag  INT  0  DoneFlag generated in the MCDevice DB 
Output parameters 
Parameter  Data type  Start value  Description 
Done  BOOL  FALSE  TRUE: Command execution 
 completed 
Busy  BOOL  FALSE  TRUE: Command is busy 
Error  BOOL  FALSE  TRUE: During command execution, 
one error has occurred. The command 
 was not completed; the cause is found in 
 the ErrorID. 
TRUE: During command execution, 
no errors occurred. 
ErrorID WORD 0 
ErrorID of the Error output parameter. 
DataLength  INT  0  Length of read data record information in bytes 
MC_ReadDriveParameter - ErrorIDs 
ErrorID
Error message  Description / to correct or avoid error 
0000 No error  - 
8001  Internal fault  Faulty or inconsistent project / software. 
8005  Command canceled because of 
input buffer overflow 
The rate at which the user program outputs commands to 
the technology is too high. 
8007  An internal error has occurred at the 
job interface 
Due to an internal problem in the S7 system, commands 
can not be accepted. 
Check the consistency of your project data, then 
download all system data to the module again. 
8043  Illegal parameter value 
Affects the input parameters ParameterNumber, 
SubIndex, NumberOfElements or DoneFlag. 
804C  Command output rate too high  The command output rate with the same instance DB was 
higher than the command interface was able to accept. 
The second command is rejected in order not to violate 
consistency the first. 
For high command output rates, always use a separate 
instance DB, or send the command again. Please note, 
that although the first accepted command may be busy, 
you may not be able to monitor it at the status outputs. 
8050  Technology not ready  During testing with breakpoints (CPU in HOLD), the 
technology function has output a new command to the 
technology. The command is rejected. 