Technical data
  Technology DBs 
CPU 317T: Technology Functions 
A5E00251798-03 
7-5 
7.2  "Positioning axis" - Technology DB 
Valid for firmware version V3.1.x of the integrated technology 
The DB is described in the integrated technology section and is read-only in the 
STEP 7 user program. 
The DB is non-retentive, irrespective of the retentivity setting of the CPU. 
Variable UpdateFlag/UpdateCounter 
See: Technology DB updates 
Variable ErrorID 
Shows the ErrorID of the last error or warning detected at the positioning axis. 
An error message can be acknowledged by calling FB 402 "MC_RESET" 
(with Axis = number of the technology DB). 
Variable ErrorBuffer[0..2] 
Buffer for the first three errors and warnings. The first error is written to ARRAY 
element 0, the second to ARRAY element 1, etc. 
This content of the buffer can be cleared by calling FB 402 "MC_RESET" 
(with Axis = number of the technology DB). 
Variable Reserve34 
The variable is reserved for internal functions. It does not contain user-relevant 
information. 