Technical data
Technology DBs 
  CPU 317T: Technology Functions 
7-40  A5E00251798-03 
ErrorID
Error message  Possible causes  To correct or avoid errors  Interrupts in
S7T Config* 
Synchroni- 
zation object
Interrupts in
S7T Config* 
Synchroni-
zation axis 
801D Reference cam or 
zero mark not found
•  The reference cam is 
out of the permissible 
range. 
•  An end position 
monitoring 
has responded. 
•  The velocity was too 
high.
Check the permissible ranges 
(e.g. max. distance between 
BERO and zero mark), the 
end position monitoring 
system and reduce the cutoff 
velocity.
 40101, 
40102 
801F Dynamic control 
circuit out of range 
•  The position or 
velocity controllers are 
not tuned 
•  Wrong sense of 
direction of the 
encoder 
•  Following error 
monitoring too 
sensitive 
•  Offset between 
velocity setpoint and 
actual value too high 
•  Check the sense of 
direction of the encoder. 
•  Check the control loop 
parameters. 
•  Modify the following error 
monitoring parameters. 
 50101 
8030 
The frequency of the 
measuring system is 
out of range 
The pulse frequency of 
the encoder signals is too 
high. 
Check the electrical 
connection of the encoder. 
Check whether the configured 
max. velocity is too low. 
 50002 
8031 Actual value 
acquisition error 
•  An incremental 
encoder is out of 
range 
•  The movement per 
position controller 
cycle exceeds the 
modulo length of the 
axis 
Check and adjust the 
configuration data for the 
adaptation of the actual value 
to mechanical requirements 
 50001, 
50013 
8032  Can not shift the 
coordinate system 
The programmed shift of 
the coordinate system 
(set or correct the actual 
position value) leads to a 
violation of the internal 
traversing range. The 
coordinate system is not 
shifted. 
Check the programmed shift 
of the coordinate system. 
 30014 
8033 Zero mark 
monitoring 
has responded 
Wrong number of 
increments between two 
zero marks of the 
encoder. 
Check the wiring and the set 
encoder resolution. 
 50006 
8040  The axis / external 
encoder is not 
enabled, or the 
wrong mode is set 
The enable signal 
required for a motion 
command is missing. 
Eliminate and acknowledge 
all queued errors and then 
enable axis operation in the 
relevant mode (e.g. position-
controlled). 
 40005 
8041  Axis not homed  A motion command is 
active and requires a 
homed axis. 
Home the axis (MC_Home). If 
this command is to be 
executed at an axis which is 
not homed, then set axis 
homing to "Homing required = 
no" 
 40108 