Technical data
  Safety Integrated Functions in 
SINAMICS Drive Systems 
  6.7 Control via PROFIsafe 
Connection of the SINAMICS S120 to the Technology CPU 
Product Information, 09/2011, A5E00480378-04 
203 
Summary 
Table 6- 4  Characteristics with and without support of the extended functions 
  With support  Without support 
StatuswordSafety and SafeSpeedLimit 
variables in the TO DB of the axis 
Contents of the variable are valid  Contents of the variables not relevant 
Errors 8140, 8142 and 8143  Signaled  Not signaled 
Error 8010 with SS1 and SS2  With SS1, suppressed until axis is at 
standstill. 
With SS2, fully suppressed. 
Occurs immediately upon selection of 
SS1 or SS2 
Release_Disable during SS1 or SS2  Has effect on drive, even during OFF3 
ramp 
Has no effect on drive. 
Follow-up mode with SS1 and SS2  Automatic follow-up mode.  No automatic follow-up mode. User 
program cannot assume follow-up 
mode. 
6.7  Control via PROFIsafe 
Introduction 
The safety functions of the drive can be controlled via terminals and the TM54F module as 
well as the PROFIsafe message frame 30. Each drive with a configured PROFIsafe in the 
drive unit represents a PROFIsafe slave (F-slave) with fail-safe communication to the F-host 
via PROFIBUS. 
A separate PROFIsafe message frame is created for each drive (PROFIsafe slot). 
Control of the basic functions via the Control Unit and Motor Module (p9601.0/p9801.0) 
terminals may be enabled in parallel. In this way, the STO, SBC, and SS1 functions 
(time controlled) can be selected via PROFIsafe as well as via the on-board terminals on the 
Control Unit and Motor Module. 