Technical data
Commissioning   
3.3 Preparing the connection to the SINAMICS 
  Connection of the SINAMICS S120 to the Technology CPU 
24  Product Information, 09/2011, A5E00480378-04 
3.3.3  Configuring in HW Config 
Introduction 
Now double-click the "Hardware" element to configure the hardware of the 
SIMATIC 300 station using the HW Config tool. 
Technology CPU: configuring the hardware 
1. Select the "SIMATIC Technology CPU" hardware catalog and add there a mounting rail 
with drag-and-drop to the configuration. 
2. Then give the mounting rail at slot 1 a power supply, e.g. PS 307 2A, the mounting rail 
at slot 2 a CPU, e.g. the Technology CPU 317T-2 DP. 
Note 
When you add the Technology CPU, pay attention to the firmware version or the order 
number of the CPU that is located on the front panel of the CPU. 
3. Click OK to confirm the displayed message for downloading the system data when the 
Technology CPU is added. 