PROGRAMING SWITCHES
CS-5000 Series Controls use two blocks of DIP switches for setup. Each block has
eight switches. Blocks carry the labels SW1 and SW2. Figure 3 (Page9) shows
the position, label and function of each switch.
IMPORTANT NOTE! With the exception of the CAL/RUN switch,the
processor only recognizes switch changes after it is RESET. Cycle
power momentarily, or briey connect the RESET and COMMON output
terminals. This is like pressing the Enter key on your computer.
SW 1
Payout — TakeUp: In PayOut (OFF), the output voltage increases as the target moves toward the
transducer. In TakeUp (ON), the output voltage decreases as the target moves
toward the transducer.
Linear — Adaptive: In Linear (OFF), the output voltage is linearly proportional to the distance between
sensor and target.
In Adaptive (ON), a control algorithm holds a loop of moving strip material at the
middle of the control range (±10% ) to compensate for the buildup (or depletion)
of material in winding applications.
HOLD: With the HOLD switch OFF, output voltage drops to zero if the control fails to see
the target within a preset number of samples. (Default is 8 samples.) With HOLD
switch ON, the output voltage stays at the last-seen value and does not drop to
zero. The HOLD function helps when targets swing outside of the sensing pattern
or are marginally reective.
Calibrate — RUN: In Calibrate (OFF) position, the control automatically seeks the target closest to
the transducer and sets its position as the Sensing Limit. The calibration target
must be farther away than 13 inches + the control range and
closer than 360 inches. Returned to RUN position, the switch
locks the Sensing Limit into memory. This setting stays in
memory until the control is recalibrated. Memory does not
depend on power. The parameters are stored in one of eight
program locations. Which one depends upon the setting
of the PreSet switches (SW2) when the Calibrate — Run
switch returns to the RUN position (ON). The parameters
stored are:
PayOut — TakeUp
Linear — Adaptive
HOLD
Range settings
Offset settings
Position of the Sensing Limit
RANGE: Four switches(5, 6, 7 & 8), used in combina-
tion set up 15 standard control ranges, from 5 inches to 70
inches. Combinations are additive as shown in Figure1.
The RANGE switches effect only Program #0. If any Preset
switches are ON, Preset Programs (1 through 7) take pre-
cedence over the range switches. If Preset Programs are
in use, (see SW2 settings) at least one range switch should
be ON.
Base
13"
Control Range
Far Relay
Trip Point
Target
Cone
Diameter
Total
Near
Relay
Trip