Installation manual
94 20/10/2004 PS10270JENAA01
Steps prior to power on
Grounding the ICS
The system must be correctly grounded in order to ensure user safety and protect against
lightning and voltage drops, and also to prevent service interruptions.
To ground the M6501L/R IP PBX:
• connect one end of the power cord to the power supply module and the other end to a
grounded mains outlet.
• combine and connect the ground braid (shield) of all the distribution cables to the ground
terminal in the installation's main distribution frame.
Power to the ICS must be switched off when you fit the power cord
Always isolate trunk lines before unplugging the mains power cord.
Never connect trunk lines while the mains power cord is unplugged.
Prise 220V
+ Terre
Réseau
de Terre
Coffret
n°1
Tête de câble à protection MFA80 28 paires
(à installer éventuellement selon les normes en vigueur)
Réseau
Public
Distribution
iinterne
Borne de masse
Fil
‡
2,5 mm2
Fil
‡
6 mm2
Fil défini avec la MFA80
A
l
i
m
e
n
t
a
t
i
o
n
1
2
Répartiteur
Téléphonie
Données
Réglettes à coupure
carte CA1
Réglettes à coupure
carte CA1
Réglettes à coupure
carte CS1
Réglettes à coupure
8 paires
Réglettes à coupure
carte RNIS T0
Réglettes à coupure
Connector strips
Connector strips
T0 ISDN card
Connector strips
8 pair
Connector strips
CS1 card
Connector strips
CA1 card
Connector strips
CA1 card
Terminal strip
Internal
distribution
Terminal
220 V
+ ground
Public
network
Data
28-pair MFA80 protective cable termination
(to be installed in accordance with the current standards)
Cabinet
No 1
P
o
w
e S
r u
p
p
l
y
Telephony
Ground terminal
>= 2.5 mm2 wire
>= 2.5 mm2 wire
Wire defined with MFA80
Ground
network