Datasheet
A
rtikelnummer
604830,604846,604863,604876,604892,604905,604920,
604936,604950,604964,604976,604989,605056,605068
Typ LiYCY
X x 0,14 mm²
Nominal voltage 0,14 – 0,34 350 V
as of / de 0,50 300 / 500 V
Test voltage 0,14 – 0,34 2000 V
as of / de 0,50 3500 V
Temperature range - 10° C + 80° C
Radiation resistance 80 Mrad
Min. bending radius 12 x Ø
Insulation resistance > 200 MOhm x km
Conductor Flexible bare copper acc. To VDE 0295 class 5
exceptions 0,14 mm² class 6 column 4 and 0,34 mm² class 3
column 2)
Conductor resistance < 142 Ohm/km (0,14mm²)
< 59 Ohm/km (0,34 mm²)
< 25 Ohm/km (0,75 mm²)
< 10 Ohm/km (2,00 mm²)
< 5 Ohm/km (4,00 mm²)
Insulation PVC flame retardant acc. to CEI 20-22 and IEC 332-3C
Screen Tinned copper braid, coverage approx. 85%
Jacket PVC flame retardant acc. to CEI 20-22 and IEC 332-3C, grey
RAL 7001
Capacitance cond./cond. Approx. 130 pF/m
Technische Änderungen unter Vorbehalt.