15. Troubleshooting
Problem
Permanent signal tone and ‘F1’
is displayed on the valve operat-
ing mechanism
Permanent signal tone and ‘F2’
is displayed on the valve operat-
ing mechanism
Permanent signal tone and ‘F3’
is displayed on the valve operat-
ing mechanism
No radio symbol displayed on
the valve operating mechanism.
The valve operating mechanism
generates a tone sequence
every hour. The valve is 30%
opened.
‘Low battery’ symbol is dis-
played. The valve operating
mechanism generates a tone
sequence every 2 minutes for
one hour.
‘LOC’ is displayed when a but-
ton is pressed
The window symbol ‘ ’ blinks
Possible cause
The valve is too tight or the
valve operating mechanism
is blocked
Control range is too large
Valve operating mechanism
is not mounted to the heat
ventilator
Control range is too small
Radio connection failure due
to interference
Heating control’s batteries
are low
Heating control’s code is not
right (or has been
misadjusted)
The valve operating mecha-
nism’s batteries are almost
empty
Button lock is activated
Radio connection failure to a
door/window contact sensor
Empty batteries
Solution
Remove the valve operating mecha-
nism
Manually check valve operation
Mount the valve operating mecha-
nism again
If necessary, consult a heating tech-
nician
Mount the valve operating mecha-
nism again
Unsuitable valve
Insert a spacer that is 1mm thick (a
washer, for example) between the
heat ventilator and the actuator
Mount the valve operating mecha-
nism again
Unsuitable valve
Install the heating control in a differ-
ent location
Replace the heating control’s bat-
teries
Transmit the current security code
to the valve operating mechanism
Replace the batteries
Deactivate the button lock
Identify and rectify the fault
Replace the batteries