Datasheet

Wide Range, Unprecedented Linearity
U.S. Patent 8,587,399
U.S. Patent 8,847,576
ACTL-1.2.18: Specications are subject to change
2150 Miller Drive, Suite A • Longmont CO 80501 • USA
sales@ctlsys.com • www.ctlsys.com
(888) 928-8663 • Fax (303) 444-2903
The Accu-CT family of standard and revenue-grade, split-core current transformers offers outstanding
linearity, very low phase angle error, easy one-handed opening and closing, with a safe 0.333 Vac low voltage output.
The standard Accu-CT meets IEEE C57.13 class 1.2 and when ordered with the Option C0.6, both models of the Accu-CT meet IEEE
C57.13 class 0.6 accuracy standards. Both models are available in standard and revenue-grade accuracies with exceptionally low-end
accuracy from 1 to 120% of primary rated current – 10x better than traditional CTs. The ACTL-1250 can also be ordered with Option C0.3
for 0.3% accuracy readings. This is especially important when SREC requirements dictate system metering accuracies meeting or exceeding
ANSI C12.1-2008 specications.
Designed specically for the WattNode
®
energy and power meters, the Accu-CT is available in two window opening sizes. The ACTL-0750
has a window opening of 0.75” x 0.75” for current measurements up to 250 amps while the ACTL-1250, with its unique oval shaped window
opening of 1.83” x 1.25” is designed for loads up to 600 amps. Each option C0.6 or C0.3 CT ships with a certicate of calibration.
The ACT series of high-accuracy split-core current transformers are UL Listed, certied by Underwriters Laboratory (UL) to meet the new
2017 NEC code requirement that CTs installed in the eld must be UL 2808 Listed under category code XOBA.
Overview
Specications
ACTL-0750 ACTL-0750 Opt C0.6 ACTL-1250 ACTL-1250 Opt C0.6 ACTL-1250 Opt C0.3
Accuracy 0.75% 0.50% 0.75% 0.50% 0.30%
Rated Amps 5, 20, 50, 100, 200, 250* 20, 50, 100, 200, 250* 250, 400, 600* 250, 400, 600* 250, 400, 600*
Optional Rated Amps 15, 30, 70, 150 15, 30, 70, 150 NA NA NA
Accuracy Class
IEEE/ANSI C57.13,
Class 1.2
IEEE/ANSI C57.13,
Class 0.6
IEEE/ANSI C57.13,
Class 1.2
IEEE/ANSI C57.13,
Class 0.6
IEEE/ANSI C57.13,
Class 0.3
CE Accuracy
IEC 60044-1
Class 1.0
IEC 60044-1
Class 0.5 S
IEC 60044-1
Class 1.0
IEC 60044-1
Class 0.5 S
IEC 60044-1 Class 0.5
and Class 0.5 S
CE Safety CE CE CE CE CE
RoHS Compliance
UL USA
UL Listed, XOBA,
UL 2808
UL Listed, XOBA,
UL 2808
UL Listed, XOBA,
UL 2808
UL Listed, XOBA,
UL 2808
UL Listed, XOBA,
UL 2808
UL Canada UL Listed - XOBA7 UL Listed - XOBA7 UL Listed - XOBA7 UL Listed - XOBA7 UL Listed - XOBA7
Standard Lead Length 8 ft (2.4m) 18 AWG 8 ft (2.4m) 18 AWG 8 ft (2.4m) 18 AWG 8 ft (2.4m) 18 AWG 8 ft (2.4m) 18 AWG
Phase Angle
±0.50 degrees
±0.25 degrees,
±0.50 degrees below 0°C
±0.50 degrees ±0.25 degrees
±0.125 degrees 10-120%
of rated current.
±0.25 from 1%-120% of
rated current.
Output Options
0.333 Vac, 1 V, 100 mA* 0.333 Vac, 1 V, 100 mA* 0.333 Vac, 1 V, 100 mA* 0.333 Vac, 1 V, 100 mA* 0.333 Vac, 1 V, 100 mA*
Operating Temperature
−40°C to 80°C −40°C to 80°C −30°C to 75°C −30°C to 75°C −30°C to 75°C
Line Frequency
50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
50/60 Hz, 60 Hz is
recommended and is
the default
Option 50 Hz Available
Not required Not required
*mA output available in 250 and 600 amp Accu-CTs.

Summary of content (2 pages)