User manual
IEC61131 User and Reference Manual 
April 22, 2008     
100 
SCADAPack and SCADAPack 32 Controllers 
For SCADAPack and SCADAPack 32 controllers, the Initialize dialog shown below appears 
when the command is selected. 
Check the Erase IEC 61131 Application selection to erase the ISaGRAF application 
program in the target controller. 
Check the Erase C Program selection to erase the C application program in the target 
controller. 
Check the Initialize Controller selection to reset the target controller to default settings.   
When this option is selected, the following actions are performed:  
  All locked variables are unlocked. 
  All Permanent Non-Volatile Modbus Registers are set to zero. 
  All digital outputs and analog outputs are cleared. 
  Data logged by all DLOG functions is erased. 
  Data logged by all FLOW and TOTAL function blocks is erased. 
  Alarm clock is cleared. 
  Serial port communication event counters are reset to zero. 
  Store and forward table is cleared. 
  Friendly IP List is cleared (if applicable). 
  The controller settings below are set to factory default values: 
-  Serial port communication parameters 
-  Modbus/IP and DNP/IP protocol settings 
-  HART modem configurations 
-  LED power control 
Note that the Ethernet port settings, where applicable, are not changed by the initialize 
controller command. 
If you are communicating using settings other than the default, the PC Communication 
Settings will have to be changed once the controller has been initialized unless 
communication was being performed via the Ethernet port.  
Click on the OK button to perform the requested initializations. 
Click on the Cancel button to exit without performing any action. 