User manual
IEC61131 User and Reference Manual 
April 22, 2008     
158 
cntr5410 
Counter input module 5410 
Description 
The cntr5410 I/O module provides four I/O channels for 5410 High Speed Counter Input 
hardware. Data for each of the four I/O channels may be connected to user-defined 
variables with the I/O connection editor. Connected variables are updated continuously with 
data read from the counter inputs. 
Set the cntr5410 module_address to match the address switches on the 5410 High Speed 
Counter Input hardware. 
The maximum count is 4,294,967,295. Counters roll over to zero when the maximum count 
is exceeded. 
I/O Connection 
Module address 
This module is assigned a unique module address between 0 
and 15. No other counter input-type module may use this 
module address. 
Library type 
IO board 
Data type 
Integer / real 
Channel type 
Input 
Number of channels 
4 
Notes 
Refer to the 5410 High Speed Counter Input Module User Manual for further information. 