User manual
IEC61131 User and Reference Manual 
April 22, 2008     
217 
  A scan_freq value of 0 synchronies the input scanning to 60Hz. 
  A scan_freq value of 1 synchronies the input scanning to 50Hz. 
  To set the scan_freq parameter, click the scan_freq icon and then select the set / 
channel parameter command from the Edit menu. The I/O Board parameter dialog is 
opened as shown below. 
  Enter the scan frequency, 0 or 1, in the Value: entry field and click OK. 
The aout_type parameter sets the analog output type for both optional analog output 
channels. 
  An aout_type value of 0 sets the output type for 0 to 20mA signals. 
  An aout_type value of 1 sets the output type for 4 to 20mA signals. 
  To set the aout_type parameter, click the aout_type icon and then select the set / 
channel parameter command from the Edit menu. The I/O Board parameter dialog is 
opened as shown below. 
  Enter the analog output type, 0 or 1, in the Value: entry field and click OK. 
AOUT Sub Module 
The AOUT sub-module provides two I/O channels for the analog output data for the 
SCADAPack sp5606 I/O hardware. Data for each of the I/O channels may be connected to 
user-defined variables with the I/O connection editor. The SCADAPack 5606 I/O hardware 
analog outputs are updated continuously with data read from the variables. 
The aout_type parameter in the AIN Sub Module sets the analog output signal type for 0 to 
20mA or 4 to 20mA. 
DIN Sub Module 
The DIN sub-module provides forty I/O channels for the digital input data from the 
SCADAPack sp5606 I/O hardware. Data for each of the I/O channels may be connected to 
user-defined variables with the I/O connection editor. Connected variables are updated 
continuously with data from the SCADAPack 5606 I/O hardware. 
The 5606 I/O Module provides thirty-two external digital inputs. These are externally wetted 
inputs. 
  Digital Input channels 0 to 31 return the digital input status for the 5606 I/O Module. 
0 = contact open (led off). 
1 = contact closed (led on). 