User manual
IEC61131 User and Reference Manual 
April 22, 2008     
229 
cominfo 
Serial port status 
Description 
The cominfo function block provides diagnostic data about a specific serial port. 
comX
clearErrorCntrs
cominfo
parityErrors
framingErrors
charOverrunError
portIOLineStatus
bufferOverrunErr
Arguments 
Inputs 
Type 
Description 
comX 
Integer 
Communication port to get status information.  
Valid values are 1 to 4. 
clearErrorCntrs 
Boolean 
Serial port counters are cleared when TRUE. 
Serial port counters accumulate when FALSE. 
Outputs 
Type 
Description 
framingErrors 
Integer 
Serial port framing errors are the number of received 
bytes where too few or too many bits were received. 
This indicates that data is being garbled or lost on the 
communication medium or that there is noise on the 
medium. 
parityErrors 
Integer 
Serial port parity errors are the number of received 
bytes where the parity bit did not match the parity of the 
data bits. This indicates that data is being garbled or lost 
on the communication medium or that there is noise on 
the medium. 
charOverrunError 
Integer 
Serial port character overrun error are the number of 
times a character was received before the previous 
character could be read. If this occurs, the processor is 
too busy to read the serial port. This may be caused by 
noise, especially if it occurs in conjunction with parity 
and framing errors. 
bufferOverrunErr 
Integer 
Serial port buffer overrun errors are the number of 
characters discarded because the 512 byte receive 
buffer is full. If a protocol is running on the port, this 
indicates that the message sent to the controller is too 
long. If no protocol is running, this indicates that the 
application program that should be reading the data 
from the port isn't. 